Application of separated heat pipe system in data center cooling

被引:131
作者
Ding, Tao [1 ]
He, Zhi Guang [1 ]
Hao, Tian [2 ]
Li, Zhen [1 ]
机构
[1] Tsinghua Univ, Dept Engn Mech, Key Lab Thermal Sci & Power Engn, Minist Educ, Beijing 100084, Peoples R China
[2] Chinese Acad Sci, Inst Opt Fine Mech & Phys, Changchun 130033, Peoples R China
关键词
Separated heat pipe system; CRAC; Energy saving; Data center cooling; THERMOSIPHON; PERFORMANCE;
D O I
10.1016/j.applthermaleng.2016.08.025
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper mainly studies the application of separated heat pipe system on data center cooling. Separated heat pipe system mainly consists of four parts: evaporator, condenser, vapor pipe and liquid pipe. Compared with traditional computer room air conditioning (CRAC) system, which is a kind of room level cooling, heat pipe cooling system is rack level cooling. There are mainly three advantages for separated heat pipe system, firstly, air flow organization is better for there is nearly no hot and cold air mixing, secondly, such system can use cold ambient air as heat sink in winter, thirdly, as the evaporator is placed directly inside the rack, heat generated from IT equipment will be soon absorbed by heat pipe system, thus there is nearly no local hot spots inside the rack. To describe the working condition of the system, there are mainly three parts in this paper. Firstly, operation performance in summer, winter and trans season is tested. Secondly, as the system can use free cold ambient air to produce chilled water, the time of using free cold ambient air is tested. Finally, T-Q diagram is used to compare the heat transfer process in heat pipe system and traditional CRAC system. The results show that, IT equipment can work in a safe and reliable environment. Besides, the heat sink temperature in heat pipe system is much higher than CRAC system and there is nearly no cold and hot air mixing in heat pipe system. In summary, heat pipe system can save more electrical energy than CRAC system. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:207 / 216
页数:10
相关论文
共 23 条
[1]  
[Anonymous], 2012, J THERM SCI ENG APPL
[2]   The property diagram in heat transfer and its applications [J].
Chen Qun ;
Xu YunChao ;
Guo ZengYuan .
CHINESE SCIENCE BULLETIN, 2012, 57 (35) :4646-4652
[3]  
Chiriac V. A., 2012, P 13 IEEE INT C SAN
[4]  
Ding T., 2015, P 14 INT C SUST EN T
[5]   Entransy - A physical quantity describing heat transfer ability [J].
Guo, Zeng-Yuan ;
Zhu, Hong-Ye ;
Liang, Xin-Gang .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2007, 50 (13-14) :2545-2556
[6]   Thermodynamic feasibility of harvesting data center waste heat to drive an absorption chiller [J].
Haywood, Anna ;
Sherbeck, Jon ;
Phelan, Patrick ;
Varsamopoulos, Georgios ;
Gupta, Sandeep K. S. .
ENERGY CONVERSION AND MANAGEMENT, 2012, 58 :26-34
[7]   Heat transfer characteristics of a two-phase closed thermosyphons using nanofluids [J].
Huminic, Gabriela ;
Huminic, Angel .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2011, 35 (03) :550-557
[8]   Experimental study of the thermal performance of thermosyphon heat pipe using iron oxide nanoparticles [J].
Huminic, Gabriela ;
Huminic, Angel ;
Morjan, Ion ;
Dumitrache, Florian .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2011, 54 (1-3) :656-661
[9]  
Iyengar M., 2012, P 28 ANN IEEE SEM TH
[10]  
Jin X., 2011, HV AC, V41, P133