Energy analysis of under-floor air distribution (UFAD) system: An office building case study

被引:29
作者
Alajmi, Ali F. [1 ]
Abou-Ziyan, Hosny Z. [1 ]
El-Amer, Wid [2 ]
机构
[1] Publ Author Appl Educ & Training, Dept Mech Engn, Coll Technol Studies, Mishref 40189, Kuwait
[2] HVAC Sect OptionOne Consultant Off, Safat 13157, Kuwait
关键词
Under-floor air distribution (UFAD) system; Thermal stratification; Occupants' and non-occupants' areas; EnergyPlus simulation; Energy saving;
D O I
10.1016/j.enconman.2013.04.003
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents the results of an experimental and theoretical investigation to evaluate an underfloor air distribution (UFAD) system existed in an office building working on hot climate. Air temperature a distribution and supply air velocity are measured in two measuring stations; each consists of eight temperature sensors which were installed to measure room air temperatures along zone height. The obtained data shows an inefficient operation of the UFAD system which deteriorates the advantages of energy saving that presumed by UFAD system. The building energy simulation program, EnergyPlus, was used to identify the best setting of UFAD system and compare it with the existed UFAD and the conventional ceiling based air distribution (CBAD) system. The simulation results show that setting of room thermostat at 26 C and supply air temperature at 18 C provides the best efficient UFAD system. Due to improper operation of the tested UFAD system, its actual consumption is found to be higher than the best simulated UFAD by 23-37% during July to October. Also, the simulation results show that the HVAC demand of UFAD is lower than CBAD by 37-39% during July-September and 51% in October. (C) 2013 Elsevier Ltd. All rights reserved.
引用
收藏
页码:78 / 85
页数:8
相关论文
共 22 条
  • [1] Addison M, 2001, COOLING VIA UNDERFLO
  • [2] Saving energy by using underfloor-air-distribution (UFAD) system in commercial buildings
    Alajmi, Ali
    El-Amer, Wid
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2010, 51 (08) : 1637 - 1642
  • [3] Proof of concept modeling of energy transfer mechanisms for radiant conditioning panels
    Ardehali, MM
    Panah, NG
    Smith, TF
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2004, 45 (13-14) : 2005 - 2017
  • [4] ASHRAE, 2010, ANSI/ASHRAE 55:2010
  • [5] The effect of ventilation aperture location of input airflow rates on the stratified flow
    Awad, Ahmad
    Badran, Omar
    Hold, Arne
    Calay, Raj
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2008, 49 (11) : 3253 - 3258
  • [6] Bauman F.S., 2003, UNDERFLOOR AIR DISTR
  • [7] Bauman F, 2007, ASHRAE J, V49, P36
  • [8] On underfloor air-conditioning of a room containing a distributed heat source and a localised heat source
    Chenvidyakarn, T.
    Woods, A. W.
    [J]. ENERGY AND BUILDINGS, 2008, 40 (07) : 1220 - 1227
  • [9] Crawley D.B., 2005, Contrasting the capabilities of buliding energy performance simulation programs
  • [10] Locating room air-conditioners at floor level for energy saving in residential buildings
    Gao, C. F.
    Lee, W. L.
    Hua, Chen
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2009, 50 (08) : 2009 - 2019