Effect of wind parks with doubly fed asynchronous generators on small-signal stability

被引:103
|
作者
Tsourakis, G. [1 ]
Nomikos, B. M. [2 ]
Vournas, C. D. [1 ]
机构
[1] Natl Tech Univ Athens, Sch Elect & Comp Engn, Athens 15780, Greece
[2] Hellen Transmiss Syst Operator, Athens 17122, Greece
关键词
Doubly fed asynchronous generator (DFAG); Wind power; Inter-area oscillations; Small-signal stability; FED INDUCTION GENERATOR; POWER-SYSTEM; LARGE-SCALE; TURBINE; IMPACT; SIMULATION; FARMS; MODEL;
D O I
10.1016/j.epsr.2008.05.018
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper investigates modes of response introduced by wind parks With doubly fed asynchronous generators (DFAGs), as well as their impact oil electromechanical oscillations in interconnected power systems. A DFAG model with detailed control loops is used, as it appears in the literature and commercial software. It is shown that under certain conditions and Without appropriate controller tuning the voltage/VAR control loop of an interconnected DFAG tends to instability. Furthermore, the effect of increased penetration of DFAGs on the stability of inter-area oscillations in a small typical power system is examined. It is shown that the effect is generally favorable, but there are cases where the inter-area mode is less damped or can even be destabilized. Improved controller tuning to avoid instability in the latter case is proposed. (C) 2008 Elsevier B.V. All rights reserved.
引用
收藏
页码:190 / 200
页数:11
相关论文
共 50 条
  • [31] Impact of PLL Control on Small-Signal Stability of Wind DFIGs
    Avila-Martinez, Regulo
    Rouco, Luis
    Garcia-Aguilar, Javier
    Renedo, Javier
    Sigrist, Lukas
    2020 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM), 2020,
  • [32] Small Signal Stability and Dynamic Analysis of Voltage-sourced Doubly-fed Wind Turbine
    Zhang X.
    Li S.
    Chen C.
    Dai L.
    Xu T.
    Dianwang Jishu/Power System Technology, 2023, 47 : 1 - 6
  • [33] Modelling and small-signal analysis of a grid connected doubly-fed induction generator
    Mei, F
    Pal, BC
    2005 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS, 1-3, 2005, : 2101 - 2108
  • [34] Control of Variable Speed Wind Turbines with Doubly Fed Asynchronous Generators for Stand-Alone Applications
    Arnaltes, Santiago
    Luis Rodriguez-Amenedo, Jose
    Montilla-DJesus, Miguel E.
    ENERGIES, 2018, 11 (01):
  • [35] Model reduction strategy of doubly-fed induction generator-based wind farms for power system small-signal rotor angle stability analysis
    Xia, S. W.
    Bu, S. Q.
    Zhang, X.
    Xu, Y.
    Zhou, B.
    Zhu, J. B.
    APPLIED ENERGY, 2018, 222 : 608 - 620
  • [36] Crowbar System in Doubly Fed Induction Wind Generators
    Salles, Mauricio B. C.
    Hameyer, Kay
    Cardoso, Jose R.
    Grilo, Ahda P.
    Rahmann, Claudia
    ENERGIES, 2010, 3 (04): : 738 - 753
  • [37] Contribution of Doubly Fed Wind Generators to Oscillation Damping
    Tsourakis, Georgios
    Nomikos, Basil M.
    Vournas, Costas D.
    IEEE TRANSACTIONS ON ENERGY CONVERSION, 2009, 24 (03) : 783 - 791
  • [38] Improved energy conversion for doubly fed wind generators
    Smith, Alexander C.
    Todd, Rebecca
    Barnes, Mike
    Tavner, Peter J.
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2006, 42 (06) : 1421 - 1428
  • [39] Power System Small-Signal Angular Stability Affected by Virtual Synchronous Generators
    Du, Wenjuan
    Fu, Qiang
    Wang, H. F.
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2019, 34 (04) : 3209 - 3219
  • [40] Small-Signal Stability Research of Grid-Connected Virtual Synchronous Generators
    Lu, Shengyang
    Zhu, Yu
    Dong, Lihu
    Na, Guangyu
    Hao, Yan
    Zhang, Guanfeng
    Zhang, Wuyang
    Cheng, Shanshan
    Yang, Junyou
    Sui, Yuqiu
    ENERGIES, 2022, 15 (19)