Improvements in the cooling capacity and the COP of a transcritical CO2 refrigeration plant operating with a thermoelectric subcooling system

被引:40
作者
Astrain, D. [1 ,2 ]
Merino, A. [1 ]
Catalan, L. [1 ,2 ]
Aranguren, P. [1 ,2 ]
Araiz, M. [1 ,2 ]
Sanchez, D. [3 ]
Cabello, R. [3 ]
Llopis, R. [3 ]
机构
[1] Univ Publ Navarra, Engn Dept, Campus Arrosadia S-N, Pamplona 31006, Spain
[2] Smart Cities Inst, Pamplona 31006, Spain
[3] Jaume I Univ, Dept Mech Engn & Construct, Campus Riu Sec S-N, Castellon de La Plana 12071, Spain
关键词
CO2; Subcooling; R744; Thermoelectricity; Transcritical; COP; Computational model; VAPOR COMPRESSION; 2-PHASE EJECTOR; DESIGN; COOLER; THERMOSIPHONS; PERFORMANCE; PELTIER; ENERGY; WATER; CYCLE;
D O I
10.1016/j.applthermaleng.2019.03.123
中图分类号
O414.1 [热力学];
学科分类号
摘要
Restrictive environmental regulations are driving the use of CO2 as working fluid in commercial vapour compression plants due to its ultra-low global warming potential (GWP(100) = 1) and its natural condition. However, at high ambient temperatures transcritical operating conditions are commonly achieved causing low energy efficiencies in refrigeration facilities. To solve this issue, several improvements have been implemented, especially in large centralized plants where ejectors, parallel compressors or subcooler systems, among others, are frequently used. Despite their good results, these measures are not suitable for small-capacity systems due mainly to the cost and the complexity of the system. Accordingly, this work presents a new subcooling system equipped with thermoelectric modules (TESC), which thanks to its simplicity, low cost and easy control, results very suitable for medium and small capacity plants. The developed methodology finds the gas-cooler pressure and the electric voltage supplied to the TESC system that maximizes the overall COP of the plant taking into account the ambient temperature, the number of thermoelectric modules used and the thermal resistance of the heat exchangers included in the TESC. The obtained results reveal that, with 20 thermoelectric modules, an improvement of 20% in terms of COP and of 25.6% regarding the cooling capacity can be obtained compared to the base cycle of CO2 of a small cooling plant refrigerated by air. Compared to a cycle that uses an internal heat exchanger IHX, the improvements reach 12.2% and 19.5% respectively.
引用
收藏
页码:110 / 122
页数:13
相关论文
共 39 条
[1]   Effective use of thermal energy at both hot and cold side of thermoelectric module for developing efficient thermoelectric water distillation system [J].
A-Madhhachi, Hayder ;
Min, Gao .
ENERGY CONVERSION AND MANAGEMENT, 2017, 133 :14-19
[2]   An experimental evaluation of the transcritical CO2 refrigerator performances using an internal heat exchanger [J].
Aprea, Ciro ;
Maiorino, Angelo .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (06) :1006-1011
[3]  
Araiz M., 2018, THE IMPORTANCE OF TH
[4]   A comparative study of different heat exchange systems in a thermoelectric refrigerator and their influence on the efficiency [J].
Astrain, D. ;
Aranguren, P. ;
Martinez, A. ;
Rodriguez, A. ;
Perez, M. G. .
APPLIED THERMAL ENGINEERING, 2016, 103 :1289-1298
[5]   Improvement of a thermoelectric and vapour compression hybrid refrigerator [J].
Astrain, D. ;
Martinez, A. ;
Rodriguez, A. .
APPLIED THERMAL ENGINEERING, 2012, 39 :140-150
[6]  
Bansal PK, 2000, INT J ENERG RES, V24, P93, DOI 10.1002/(SICI)1099-114X(200002)24:2<93::AID-ER563>3.0.CO
[7]  
2-6
[8]   Design and experimental investigation of a novel thermoelectric water dispenser unit [J].
Caglar, Ahmet .
APPLIED THERMAL ENGINEERING, 2019, 149 :822-828
[9]   Performance analysis and assessment of thermoelectric micro cooler for electronic devices [J].
Cai, Yang ;
Liu, Di ;
Zhao, Fu-Yun ;
Tang, Jian-Feng .
ENERGY CONVERSION AND MANAGEMENT, 2016, 124 :203-211
[10]  
Catalan Gil J., 2017, EVALUACI6O ENERGETIC