Impact of Wind Generation on Power Swing Protection

被引:47
作者
Haddadi, Aboutaleb [1 ]
Kocar, Ilhan [1 ]
Karaagac, Ulas [2 ]
Gras, Henry [1 ]
Farantatos, Evangelos [3 ]
机构
[1] Montreal Polytech, Montreal, PQ H3T 1J4, Canada
[2] Hong Kong Polytech Univ, Dept Elect Engn, Hong Kong, Peoples R China
[3] Elect Power Res Inst, 3412 Hillview Ave, Palo Alto, CA 94304 USA
关键词
Power system protection; wind energy integration; power swing protection; power system faults; power system simulation; DISTANCE PROTECTION;
D O I
10.1109/TPWRD.2019.2896135
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Large-scale integration of wind generation changes the power swing characteristics of a power system and may result in the misoperation of legacy power swing protection schemes. This paper presents a qualitative study on the impact of wind generation on power swing protection. The objective is to provide an understanding of the problem through case studies and present possible solutions and adjustments in protection schemes to ensure the efficiency of protection under large-scale integration of wind generation. The misoperation of power swing protection functions, namely power swing blocking and out-of-step tripping (OST), as a result of increased wind generation levels, are shown through case studies. It is also shown that the electrical center of a power system may move due to wind generation. In this case, it would be necessary to revise the optimal location of the OST protection. Finally, the impact of various factors, such as wind generator type, control scheme and fault-ride-through function, and wind generation level and capacity are investigated to determine the key features that need to be accounted for in practical protection studies.
引用
收藏
页码:1118 / 1128
页数:11
相关论文
共 21 条
[1]  
[Anonymous], 2005, WGD6 IEEE PSRC
[2]  
[Anonymous], 2004, WGD29 IEEE PSRC
[3]  
[Anonymous], 2003, GRID COD HIGH EXTR H
[4]   Impact of Increased Penetration of DFIG-Based Wind Turbine Generators on Transient and Small Signal Stability of Power Systems [J].
Gautam, Durga ;
Vittal, Vijay ;
Harbour, Terry .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2009, 24 (03) :1426-1434
[5]   Distance Protection of AC Grid With HVDC-Connected Offshore Wind Generators [J].
He, Lina ;
Liu, Chen-Ching ;
Pitto, Andrea ;
Cirio, Diego .
IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (02) :493-501
[6]   Distance Protection of Lines Emanating From Full-Scale Converter-Interfaced Renewable Energy Power Plants-Part II: Solution Description and Evaluation [J].
Hooshyar, Ali ;
Azzouz, Maher A. ;
El-Saadany, Ehab F. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (04) :1781-1791
[7]   Distance Protection of Lines Emanating From Full-Scale Converter-Interfaced Renewable Energy Power Plants-Part I: Problem Statement [J].
Hooshyar, Ali ;
Azzouz, Maher A. ;
El-Saadany, Ehab F. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (04) :1770-1780
[8]   Distance Protection of Lines Connected to Induction Generator-Based Wind Farms During Balanced Faults [J].
Hooshyar, Ali ;
Abdelkhalek, Maher ;
El-Saadany, Ehab F. .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2014, 5 (04) :1193-1203
[9]  
IEEE NERC Task Force on Short-Circuit and System Performance Impact of Inverter Based Generation, 2018, PESTR68 IEEENERC TAS
[10]  
Karaagac U., 2017, Simulation models for wind parks with variable speed wind turbines in emtprv