Introducing Mutual Heating Effects in the Ladder-Type Soil Model for the Dynamic Thermal Rating of Underground Cables

被引:20
作者
Diaz-Aguilo, Marc [1 ]
de Leon, Francisco [1 ]
机构
[1] NYU, Dept Elect & Comp Engn, Brooklyn, NY 11201 USA
关键词
Mutual heating; power systems; power system measurement; real-time thermal rating; thermal modeling; underground cables; SYSTEMS;
D O I
10.1109/TPWRD.2015.2390072
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The proper modeling of the transient thermal behavior of mutual heating effects between underground power cables is very important for the rating of transmission and distribution cables. The IEC standards proposed an accurate model based on exponential integrals that it can be difficult to implement in basic electrical software. The model is not consistent with the layered modeling of the cable thermal resistances. In this paper, a simple and easy-to-use alternative model is presented. It consists of injecting the correct current at the right position of the RC circuit representing the soil. The new model can accurately reproduce the full physics of the transient phenomenon and is consistent with the modeling of the cable used in the IEC standards themselves. The new model is tested and validated against numerous finite-element simulations for realistic cable installations.
引用
收藏
页码:1958 / 1964
页数:7
相关论文
共 26 条
[1]  
Anders G.J., 1997, RATING ELECT POWER C
[2]   Advanced modeling techniques for dynamic feeder rating systems [J].
Anders, GJ ;
Napieralski, A ;
Zubert, M ;
Orlikowski, M .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2003, 39 (03) :619-626
[3]  
[Anonymous], 1994, 8351994 IEEE
[4]  
[Anonymous], P IEEE POW EN SOC GE
[5]  
[Anonymous], 1989, 608531 IEC
[6]   METHODOLOGY FOR REAL-TIME CALCULATION OF TEMPERATURE RISE AND DYNAMIC RATINGS FOR DISTRIBUTION-SYSTEM DUCT BANKS [J].
BENYAACOV, GZ ;
BOHN, JG .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (12) :4604-4610
[7]  
CIGRE Working Group 21. 02, 1985, ELECTRA, V87, P41
[8]  
de Leon F., Major factors affecting cable ampacity
[9]  
Diaz-Aguilo M., 2014, IET SCI MEA IN PRESS
[10]  
DIAZAGUILO M, 2014, P IEEE POWER ENERGY, V1, P1