A Field Study of Aging in Paper-Oil Insulation Systems

被引:64
|
作者
Lelekakis, Nick [1 ]
Guo, Wenyu [1 ]
Martin, Daniel [1 ]
Wijaya, Jaury [1 ]
Susa, Dejan [2 ]
机构
[1] Monash Univ, Ctr Power Transformer Monitoring Diagnost & Life, Clayton, Vic 3800, Australia
[2] SINTEF, Energy Res Dept, N-7034 Trondheim, Norway
关键词
power transformer; paper aging; degree of polymerization; furan analysis;
D O I
10.1109/MEI.2012.6130527
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The paper used to insulate the windings of power transformers is mostly made from wood pulp, a cellulosic material. Over decades the paper is slowly attacked by water, oxygen, oil acids, and high temperatures and eventually degrades to the point where it is no longer an effective insulator. The transformer is then likely to fail. Power utilities need to know when a transformer is nearing the end of its useful life in order to plan its replacement. However, a problem with monitoring the condition of the paper within a transformer is that it may be difficult to obtain a sample to test. Furthermore, a particular sample may not accurately reflect the overall paper condition. A power transformer operating in Australia failed in 2010. Thus we had the opportunity to study the paper condition at various points within the transformer and evaluate the validity of the current understanding of paper aging. In this article we discuss the mechanisms of cellulose degradation, and the associated equations, and apply them to the paper insulation in the failed transformer. © 2012 IEEE.
引用
收藏
页码:12 / 19
页数:8
相关论文
共 50 条
  • [41] Convective Heat Transfer Coefficient of Insulation Paper-Oil Contact Surface of Transformer Vertical Oil Channel
    Luo, Chuan
    Li, Chuan
    Wan, Xiaorong
    Zhao, Zhengang
    COATINGS, 2023, 13 (01)
  • [42] Influence of Temperature and Moisture Level in Paper-Oil Insulation on the Parameters of the Cole-Cole Model
    Wolny, Stefan
    Adamowicz, Artur
    Lepich, Marek
    IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (01) : 246 - 250
  • [43] Precise Measurements of the Temperature Influence on the Complex Permittivity of Power Transformers Moistened Paper-Oil Insulation
    Zukowski, Pawel
    Rogalski, Przemyslaw
    Kierczynski, Konrad
    Koltunowicz, Tomasz N.
    ENERGIES, 2021, 14 (18)
  • [44] Assessment of Paper-oil Insulation under Copper Corrosion Using Polarization and Depolarization Current Measurements
    Flora, S. Daisy
    Rajan, J. Sundara
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (03) : 1523 - 1533
  • [45] The application of the Cole-Cole model for determining the characteristics of depolarization current of paper-oil insulation
    Wolny, Stefan
    Zdanowski, Maciej
    PRZEGLAD ELEKTROTECHNICZNY, 2008, 84 (03): : 29 - 31
  • [46] Study on generation rate of characteristic products of oil-paper insulation aging
    Liao, Rui-Jin
    Feng, Yun
    Yang, Li-Jun
    Xiang, Bin
    Liu, Gang
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2008, 28 (10): : 142 - 147
  • [47] Study on the influence of preload on the thermal aging of transformer oil-paper insulation
    Liu J.
    Wang F.-Y.
    Dianji yu Kongzhi Xuebao/Electric Machines and Control, 2020, 24 (06): : 127 - 134
  • [48] Understanding and analysis on frequency dielectric parameter for quantitative diagnosis of moisture content in paper-oil insulation system
    Liao, Ruijin
    Liu, Jiefeng
    Yang, Lijun
    Gao, Jun
    Zhang, Yiyi
    Lv, YanDong
    Zheng, Hanbo
    IET ELECTRIC POWER APPLICATIONS, 2015, 9 (03) : 213 - 222
  • [49] The assessment of the influence of temperature of selected parameters of the approximation method of depolarization current analysis of paper-oil insulation
    Wolny, Stefan
    Kedzia, Jozef
    JOURNAL OF NON-CRYSTALLINE SOLIDS, 2010, 356 (11-17) : 809 - 814
  • [50] Research and Field Application of Oil-paper Insulation Material Aging State Based on FDS
    Li Dandan
    Fan Yongqiang
    Wang Yaping
    Yue Yonggang
    Reng Ming
    INTERNATIONAL CONFERENCE ON ENERGY, POWER AND MECHANICAL ENGINEERING (EPME2019), 2020, 793