Radio interference excitation function of conductor bundles based on cage test results and comparison with long-term data

被引:11
作者
He, Wang-ling [1 ]
He, Jun-jia [1 ]
Wan, Bao-quan [2 ]
Chen, Yu-chao [2 ]
Pei, Chun-ming [2 ]
Zhang, Jian-gong [1 ,2 ]
Zhang, Jin [1 ,3 ]
机构
[1] Huazhong Univ Sci & Technol, Sch Elect & Elect Engn, Wuhan 430074, Peoples R China
[2] China Elect Power Res Inst, AC Electromagnet Environm Dept, Wuhan, Peoples R China
[3] China Elect Power Inst, Qual Inspect & Test Ctr Elect Equipment Power Ind, Wuhan, Peoples R China
关键词
TRANSMISSION-LINES; CORONA PERFORMANCE; PREDETERMINATION; NOISE;
D O I
10.1049/iet-smt.2014.0224
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A reasonable excitation function is vital to make a precise evaluation about the radio interference (RI) level of ultra-high-voltage (UHV) AC power lines. To obtain this function, a large number of RI measurements in heavy rain condition were done using different conductor bundles in a corona cage. Then, the excitation function in heavy rain condition was obtained by least-square fitting these measured values. After that, the validity of this function was verified with the statistical data measured from the Hubei long-term station, which is located under the operating 1000 kV Jindongnan-Nanyang-Jingmen UHV AC transmission lines. It turns out that the deviation between the prediction and the long-term average value is 1.1 dB in heavy rain condition, and 1.3 dB in fair weather condition. In addition, the long-term data measured in Hubei Station show that the conversion laws of RI at different weather conditions in International Special Committee on Radio Interference (CISPR)18 are also applicable to 1000 kV UHV transmission lines.
引用
收藏
页码:621 / 627
页数:7
相关论文
共 20 条
[1]  
Adams G E, 1956, IEEE T, V75, P411
[2]  
Alexandrov A., 1996, EHV EQUIPMENT ITS SU
[3]  
[Anonymous], 2010, 18 CISPR
[4]  
Begamudre R.D., 2008, EXTRAHIGH VOLTAGE AC, V3rd
[5]  
Comber M.G., 1982, TRANSMISSION LINE RE
[6]   THEORY OF EXCITATION-FUNCTION - DEMONSTRATION OF ITS PHYSICAL MEANING [J].
GARY, CH .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1972, PA91 (01) :305-&
[7]   RADIO NOISE, AUDIBLE NOISE, AND CORONA LOSS OF EHV AND UHV TRANSMISSION LINES UNDER RAIN - PREDETERMINATION BASED ON CAGE TESTS [J].
JUETTE, GW ;
ZAFFANELLA, LE .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1970, PA89 (06) :1168-+
[8]  
Maruvada PS., 2000, CORONA PERFORMANCE H
[9]   PREDETERMINATION OF RADIO-INTERFERENCE LEVEL OF HIGH-VOLTAGE TRANSMISSION-LINES .1. PREDETERMINATION OF EXCITATION-FUNCTION [J].
MOREAU, MR ;
GARY, CH .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1972, PA91 (01) :284-&
[10]   COMPARISON OF SEVERAL METHODS FOR CALCULATING POWER-LINE ELECTROMAGNETIC-INTERFERENCE LEVELS AND CALIBRATION WITH LONG-TERM DATA [J].
OLSEN, RG ;
SCHENNUM, SD ;
CHARTIER, VL .
IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (02) :903-913