A Setting-Free Differential Protection for Power Transformers Based on Second Central Moment

被引:28
作者
Esponda, Hector [1 ]
Vazquez, Ernesto [1 ]
Andrade, Manuel A. [1 ]
Johnson, Brian K. [2 ]
机构
[1] Univ Autonoma Nuevo Leon, Dept Elect Engn, Monterrey 66455, Mexico
[2] Univ Idaho, Dept Elect & Comp Engn, Moscow, ID 83843 USA
关键词
Power transformer; differential protection; inrush current; second central moment; RTDS; TO-TURN FAULTS; INRUSH CURRENTS; INTERNAL FAULTS; DISCRIMINATION; IDENTIFY; BEHAVIOR;
D O I
10.1109/TPWRD.2018.2889471
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper describes a differential algorithm for the protection of a three-phase transformer to differentiate transient phenomena, such as inrush currents and external faults from solid and turn-to-turn faults. This algorithm is based on the behavior of the second central moment (SCM) to identify the kind of event. Instantaneous differential currents are used as input signals to the algorithm once they are filtered and normalized. The algorithm compares the magnitude of the SCM with an established threshold based on the binomial distribution to achieve a successful identification of the event. If the magnitude of the SCM is above the limit, the algorithm identifies the event as a fault condition. Otherwise, the event is determined as a transient event or a steady-state condition. The threshold is setting-free if the transformer parameters are changed or if the harmonic content of the differential current varies. Also, the threshold does not have to be recalculated if the power system is modified. The D index was introduced to improve the fault-detection time when the current transformers experience saturation. This index uses the magnitude of the SCM as a basis and is compared with an established limit to detect the fault current. Both indices run in parallel, and if any of them does cross its respective threshold, a fault condition is determined. The algorithm is tested in a real-time digital simulator and is implemented inMATLAB. The algorithm was compared against the conventional differential protection with harmonic restraint to evaluate the performance of both indices in critical conditions. The results validate the performance of the algorithm and indicate that it can be the basis of a new algorithm to protect power transformers.
引用
收藏
页码:750 / 759
页数:10
相关论文
共 41 条
[1]   Power transformer differential protection using current and voltage ratios [J].
Ali, E. ;
Helal, A. ;
Desouki, H. ;
Shebl, K. ;
Abdelkader, S. ;
Malik, O. P. .
ELECTRIC POWER SYSTEMS RESEARCH, 2018, 154 :140-150
[2]  
[Anonymous], 2012, The Royal College of Surgeons of England/The British Society for Disability and Oral Health, P1
[3]   Hyperbolic S-transform-based method for classification of external faults, incipient faults, inrush currents and internal faults in power transformers [J].
Ashrafian, A. ;
Rostami, M. ;
Gharehpetian, G. B. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2012, 6 (10) :940-950
[4]   Application of a Recursive Phasor Estimation Method for Adaptive Fault Component Based Differential Protection of Power Transformers [J].
Ashrafian, Abdolaziz ;
Mirsalim, Mojtaba ;
Masoum, Mohammad A. S. .
IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, 2017, 13 (03) :1381-1392
[5]   Effect of transformer winding mechanical defects, internal and external electrical faults and inrush currents on performance of differential protection [J].
Bagheri, Sajad ;
Moravej, Zahra ;
Gharehpetian, Gevork B. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (10) :2508-2520
[6]   A GDSC-Based Technique to Distinguish Transformer Magnetizing From Fault Currents [J].
Batista, Ygo Neto ;
de Souza, Helber Elias Paz ;
dos Santos Neves, Francisco de Assis ;
Dias Filho, Roberto Feliciano .
IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (02) :589-599
[7]  
Behrendt K., 2011, SEL J. Reliable Power, V2, P36
[8]  
Benmouyal G., 1999, PROC 26 ANN W PROTEC, P1
[9]   A better bound on the variance [J].
Bhatia, R ;
Davis, C .
AMERICAN MATHEMATICAL MONTHLY, 2000, 107 (04) :353-357
[10]   Correlation analysis of waveforms in nonsaturation zone-based method to identify the magnetizing inrush in transformer [J].
Bi, D. Q. ;
Zhang, X. A. ;
Yang, H. H. ;
Yu, G. W. ;
Wang, X. H. ;
Wang, W. J. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (03) :1380-1385