The energy absorption capability and time-to-failure of varistors used in station-class metal-oxide surge arresters

被引:45
|
作者
Ringler, KG
Kirkby, P
Erven, CC
Lat, MV
Malkiewicz, TA
机构
[1] Ontario Hydro Technologies, Toronto
关键词
metal-oxide surge arresters; varistors; energy absorption capability; current pulses; current density; current duration; testing; confidence limits; failure probability; failure modes; time-to-failure; standards;
D O I
10.1109/61.568242
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Varistors for use in station-class surge arresters were tested to destruction to determine their energy absorption capability at current levels ranging from 0.8 A(peak) to 35 kA(peak). Typical mean values increased from 400-600 J/cm(3) at the lower current end to 1,600-2,000 J/cm(3) at 35 kA(peak). The product of the mean time-to-failure and the mean current was found to be a constant over five orders of magnitude. The varistor failure mode was found to be a characteristic of the current magnitude. It is recommended that standard test methods be developed for the energy absorption capability of metal-oxide surge arresters, and be included in relevant standards.
引用
收藏
页码:203 / 212
页数:10
相关论文
共 14 条
  • [1] Failure study of metal-oxide surge arresters
    Akbar, M
    Ahmad, M
    ELECTRIC POWER SYSTEMS RESEARCH, 1999, 50 (02) : 79 - 82
  • [2] DEVELOPMENT OF METAL-OXIDE VARISTORS FOR GAS-INSULATED SURGE ARRESTERS
    POTTER, ME
    SOKOLY, TO
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (07): : 2217 - 2220
  • [3] AN EXAMINATION OF THE POLLUTION PERFORMANCE OF GAPPED AND GAPLESS METAL-OXIDE STATION CLASS SURGE ARRESTERS
    LENK, DW
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1984, 103 (02): : 337 - 344
  • [4] Degradation Effects on Energy Absorption Capability and Time to Failure of Low Voltage Metal Oxide Varistors
    Khanmiri, Dawood Talebi
    Ball, Roy
    Lehman, Brad
    IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (05) : 2272 - 2280
  • [5] Recent Experimental Findings on the Single and Multi-Impulse Energy Handling Capability of Metal-Oxide Varistors for Use in High-Voltage Surge Arresters
    Tuczek, Maximilian Nikolaus
    Hinrichsen, Volker
    IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (05) : 2197 - 2205
  • [6] New Manufacturing Process for the Metal Oxide Varistors used on Low Voltage Surge-Arresters
    Paun, Adrian Constantin
    Vatau, Doru
    Frigura-Iliasa, Flaviu Mihai
    Andea, Petru
    Frigura-Iliasa, Mihaela
    Balcu, Florin Ionel
    PROCEEDINGS OF THE 2017 18TH INTERNATIONAL SCIENTIFIC CONFERENCE ON ELECTRIC POWER ENGINEERING (EPE), 2017, : 351 - 354
  • [7] Comments on metal oxide surge arresters surges energy absorption capacity
    Martinez, MLB
    Zanetta, LC
    CONFERENCE RECORD OF THE 1996 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 1996, : 498 - 501
  • [8] Failure mode tests for distribution type metal-oxide surge arresters with polymeric housing
    Colombo, E
    deNigris, M
    Sironi, A
    IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (01) : 240 - 252
  • [9] Comparisons of in-service and laboratory failure modes of metal-oxide distribution surge arresters
    Darveniza, M
    Saha, TK
    Wright, S
    2000 IEEE POWER ENGINEERING SOCIETY WINTER MEETING - VOLS 1-4, CONFERENCE PROCEEDINGS, 2000, : 2093 - 2100
  • [10] Reliability Analysis of Low-Voltage Metal-Oxide Surge Arresters Using Accelerated Failure Time Model
    Bokoro, Pitshou
    Doorsamy, Wesley
    IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (06) : 3139 - 3146