Analysis of Pressure Safety Valves for fire protection on offshore oil and gas installations

被引:18
作者
Bjerre, Michael [1 ]
Eriksen, Jacob G. I. [1 ,2 ]
Andreasen, Anders [2 ]
Stegelmann, Carsten [2 ]
Mando, Matthias [3 ]
机构
[1] Aalborg Univ, Niels Bohrs Vej 8, DK-6700 Esbjerg, Denmark
[2] Ramboll Oil & Gas, Willemoesgade 2, DK-6700 Esbjerg, Denmark
[3] Aalborg Univ, Dept Energy Technol, Pontoppidanstrcede 101, DK-9220 Aalborg, Denmark
关键词
PSV; Fire protection; Pressure vessel; Oil and gas; Offshore installations; Fire simulation; THERMAL RESPONSE; LPG TANKS; MODEL;
D O I
10.1016/j.psep.2016.10.008
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
The effectiveness of fire Pressure Safety Valves (PSV) has been investigated when offshore process equipment is exposed to a fire. Simulations of several typical offshore pressure vessels have been performed using the commercial software VessFire. The pressure vessels are exposed to a small jet fire, large jet fire, and a pool fire on both the wetted and unwetted part of the vessels. Rupture times of the vessels are calculated by comparing the pressure in the vessel with the tensile strength of the material. Rupture times are then compared for the vessels, with and without a PSV, in order to see the effect of the installed PSV. It is found that when a fire affects the unwetted part of a vessel, the PSV offers only minor or no additional protection. When a fire affects the wetted part of a vessel, the PSV relieve the inventory as designed. It is argued that PSVs provide insufficient fire protection for typical offshore fire scenarios and that Blowdown Valves and Passive Fire Protection should be considered as alternatives. (C) 2016 Institution of Chemical Engineers. Published by Elsevier B.V. All rights reserved.
引用
收藏
页码:60 / 68
页数:9
相关论文
共 21 条
[1]  
[Anonymous], 2007, 14C API
[2]  
[Anonymous], 2014, 521 API
[3]  
[Anonymous], 2014, 520 API
[4]  
AYDEMIR NU, 1988, J HAZARD MATER, V20, P239, DOI 10.1016/0304-3894(88)87015-8
[5]  
Berge G., PROTECTION PROCESS E
[6]  
Berge G., 2005, 24 INT C OFFSH MECH
[7]   FIRE ENGULFMENT OF LPG TANKS - HEATUP, A PREDICTIVE MODEL [J].
BEYNON, GV ;
COWLEY, LT ;
SMALL, LM ;
WILLIAMS, I .
JOURNAL OF HAZARDOUS MATERIALS, 1988, 20 (1-3) :227-238
[8]  
Birk A.M., 2006, J LOSS PREV PROCESS, V19
[10]  
Dalzell G., 1997, PROCESS SAF ENVIRON