Wide-Area Backup Protection Against Asymmetrical Faults Using Available Phasor Measurements

被引:20
作者
Azizi, Sadegh [1 ]
Liu, Gaoyuan [2 ]
Dobakhshari, Ahmad Salehi [3 ]
Terzija, Vladimir [2 ]
机构
[1] Univ Leeds, Sch Elect & Elect Engn, Leeds LS2 9JT, W Yorkshire, England
[2] Univ Manchester, Sch Elect & Elect Engn, Manchester M13 9PL, Lancs, England
[3] Univ Guilan, Fac Engn, Rasht 4199613776, Iran
关键词
Circuit faults; Mathematical model; Phasor measurement units; Current measurement; Synchronization; Transmission line measurements; Voltage measurement; Least squares method; Sequence circuits; Time-synchronization errors; Wide area backup protection; TRANSMISSION; FORMULATION; PLACEMENT; LOCATION; SCHEME;
D O I
10.1109/TPWRD.2019.2960352
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a robust and computationally efficient wide-area backup protection (WABP) scheme against asymmetrical faults on transmission systems using available synchronized/unsynchronized phasor measurements. Based on the substitution theorem, the proposed scheme replaces the faulted line with two suitable current sources. This results in a linear system of equations for WABP, with no need of full system observability by measurement devices. The identification of the faulted line is attributed to the sum of squared residuals (SoSR) of the developed system of equations. To preserve accuracy, the scheme limits the calculations to the assessment of the negative-sequence circuit of the gird. Relevant practical aspects that have not been properly addressed in the literature, namely the non-simultaneous opening of circuit breakers (CBs) and their single-pole tripping for single-phase to ground faults are investigated. The linearity of the formulations derived removes concerns over convergence speed and potential time-synchronization challenges. The proposed scheme is able to identify the faulted line and retain this capability for hundreds of milliseconds following the fault inception. More than 20 000 simulations conducted on the IEEE 39-bus test system verify the effectiveness of the proposed WABP scheme.
引用
收藏
页码:2032 / 2039
页数:8
相关论文
共 34 条
[1]  
Anderson P.M., 1999, Power system protection
[2]  
[Anonymous], 2011, IEEE Std, P1, DOI 10.1109/IEEESTD.2011.6111219
[3]  
[Anonymous], 2002, Network Protection Automation Guide
[4]   From Available Synchrophasor Data to Short-Circuit Fault Identity: Formulation and Feasibility Analysis [J].
Azizi, Sadegh ;
Sanaye-Pasand, Majid .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2017, 32 (03) :2062-2071
[5]   Locating Faults on Untransposed, Meshed Transmission Networks Using a Limited Number of Synchrophasor Measurements [J].
Azizi, Sadegh ;
Sanaye-Pasand, Majid ;
Paolone, Mario .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2016, 31 (06) :4462-4472
[6]   A Straightforward Method for Wide-Area Fault Location on Transmission Networks [J].
Azizi, Sadegh ;
Sanaye-Pasand, Majid .
IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (01) :264-272
[7]   Optimal PMU Placement by an Equivalent Linear Formulation for Exhaustive Search [J].
Azizi, Sadegh ;
Dobakhshari, Ahmad Salehi ;
Sarmadi, S. Arash Nezam ;
Ranjbar, Ali Mohammad .
IEEE TRANSACTIONS ON SMART GRID, 2012, 3 (01) :174-182
[8]  
Blackburn J.L., 2014, PROTECTIVE RELAYING, V4th ed.
[9]  
Desoer C.A., 2009, BASIC CIRCUIT THEORY
[10]   Wide-Area Fault Location of Transmission Lines by Hybrid Synchronized/Unsynchronized Voltage Measurements [J].
Dobakhshari, Ahmad Salehi .
IEEE TRANSACTIONS ON SMART GRID, 2018, 9 (03) :1869-1877