Numerical simulation of thermal stratification and air quality in an underfloor air distribution system (UFAD)

被引:3
|
作者
Stephen Lopez, Neil [1 ]
Kay Galeos, Selena [1 ]
Raphael Calderon, Brian [1 ]
Roy Dominguez, David [1 ]
Joseph Uy, Bryan [1 ]
Iyengar, Rupesh [2 ]
机构
[1] De La Salle Univ, Mech Engn Dept, Manila, Philippines
[2] Index Workshop LLP, Singapore, Singapore
来源
INTERNATIONAL CONFERENCE ON SUSTAINABLE ENERGY AND GREEN TECHNOLOGY 2019 | 2020年 / 463卷
关键词
COMFORT;
D O I
10.1088/1755-1315/463/1/012021
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
The penetration of underfloor air distribution systems (UFAD) in residential and commercial air conditioning has been rather slow. The most notable applications would be on data centers, where thermal stratification requirements are more demanding. The present study supports and strengthens recent work in the design and development of UFAD systems, by augmenting literature on proper vent positioning and design. In UFAD systems where thermal stratification is more pronounced, significant energy savings may be achieved through proper positioning of supply and return vents. Using a validated numerical simulation model in ANSYS CFX, four UFAD vent layouts are investigated with regards to their implications on thermal stratification and indoor air quality. Results show that not only ventilation layout, but also vent type selection can significantly affect the performance of a UFAD system. Spreading multiple, smaller supply diffusers is preferable than having large supply diffusers on the perimeter of the rooms, both from a temperature distribution and indoor air quality perspective. Notably, air flow is significantly poor in the perimeter layout, causing warmer temperature at the center of the room.
引用
收藏
页数:6
相关论文
共 50 条
  • [1] Computational Fluid Dynamics Simulation of Indoor Air Quality and Thermal Stratification of an Underfloor Air Distribution System (UFAD) with Various Vent Layouts
    Stephen Lopez, Neil
    Kay Galeos, Selena
    Raphael Calderon, Brian
    Roy Dominguez, David
    Joseph Uy, Bryan
    Iyengar, Rupesh
    FDMP-FLUID DYNAMICS & MATERIALS PROCESSING, 2021, 17 (02): : 333 - 347
  • [2] Impact of plenum on air distribution and thermal stratification in underfloor air distribution system
    Niu, Jianlei
    Shen, Chong
    Gao, Naiping
    Dong, Kun
    Tongji Daxue Xuebao/Journal of Tongji University, 2014, 42 (03): : 454 - 459
  • [3] Underfloor air distribution: Thermal stratification
    Webster, T
    Bauman, F
    Reese, J
    ASHRAE JOURNAL, 2002, 44 (05) : 28 - +
  • [4] Alternative air conditioning technologies underfloor air distribution (UFAD)
    Webster, Tom
    Energy Engineering: Journal of the Association of Energy Engineering, 2005, 102 (06): : 58 - 77
  • [5] Thermal decay in underfloor air distribution (UFAD) systems: Fundamentals and influence on system performance
    Lee, Kwang Ho
    Schiavon, Stefano
    Bauman, Fred
    Webster, Tom
    APPLIED ENERGY, 2012, 91 (01) : 197 - 207
  • [6] Numerical study on temperature stratification in a room with underfloor air distribution system
    Kong, Qiongxiang
    Yu, Bingfeng
    ENERGY AND BUILDINGS, 2008, 40 (04) : 495 - 502
  • [7] Computational fluid dynamics analysis on underfloor air distribution (UFAD) system in BTLAB
    Chen, Huajun
    Chen, Yitung
    Hsieh, Hsuan-Tsung
    Tan, Liangcai
    Novosel, Davor
    PROCEEDINGS OF THE ASME/JSME THERMAL ENGINEERING SUMMER HEAT TRANSFER CONFERENCE 2007, VOL 1, 2007, : 425 - 431
  • [8] Heat transfer pathways in underfloor air distribution (UFAD) systems
    Bauman, Fred S.
    Jin, Hui
    Webster, Tom
    ASHRAE TRANSACTIONS 2006, VOL 112, PT 2, 2006, 112 : 567 - +
  • [9] Saving energy by using underfloor-air-distribution (UFAD) system in commercial buildings
    Alajmi, Ali
    El-Amer, Wid
    ENERGY CONVERSION AND MANAGEMENT, 2010, 51 (08) : 1637 - 1642
  • [10] Experimental parametric study on the temperature distribution of an underfloor air distribution (UFAD) system with grille diffusers
    Zhang, Kai
    Zhang, Xiaosong
    Li, Shuhong
    Jin, Xing
    INDOOR AND BUILT ENVIRONMENT, 2016, 25 (05) : 748 - 757