DC Characterization of Isoparaffinic Insulation Oil

被引:2
作者
Lavesson, Nils [1 ]
Walfridsson, Lars [1 ]
Schiessling, Joachim [1 ]
机构
[1] ABB Power Grids Res, Forskargrand 7, S-72178 Vasteras, Sweden
关键词
oil insulation; HVDC insulation; power transformer insulation; impregnated insulation; electrooptic Kerr effect; conductivity measurement; FIELD;
D O I
10.1109/TDEI.2020.008729
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Converter transformers in HVDC stations are subject to both AC and DC stresses. With new oils entering the market it is important that these are characterized both for AC and DC. This paper focuses on DC characterization of one such oil, which is an isoparaffinic oil produced using a gas to liquid production process. The results are compared to mineral oil as reference. The isoparaffinic oil is shown to have a very high resistivity. In fact, the resistivity is so high that it is more resistive than impregnated pressboard with low moisture content. This is a dielectric risk which must be considered if the oil is to be used in converter transformers.
引用
收藏
页码:1525 / 1528
页数:4
相关论文
共 13 条
  • [1] [Anonymous], 2004, 602472004 IEC
  • [2] [Anonymous], 2017, 6007657129 IECIEEE
  • [3] [Anonymous], 1998, 616201998 IEC
  • [4] Denat A., 2011, IEEE INT C DIEL LIQ
  • [5] ELECTRICAL-FIELD DISTRIBUTION IN TRANSFORMER OIL
    GAFVERT, U
    JAKSTS, A
    TORNKVIST, C
    WALFRIDSSON, L
    [J]. IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1992, 27 (03): : 647 - 660
  • [6] Modeling and measurements of electric fields in composite oil/cellulose insulation
    Gafvert, Uno
    Hjortstam, Olof
    Serdyuk, Yuriy
    Tornkvist, Christer
    Walfridsson, Lars
    [J]. 2006 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2006, : 154 - 157
  • [7] Kuchler A., 2010, EVALUATION CONDUCTIV
  • [8] Kuchler A., 2016, HVDC TRANSFORMER INS
  • [9] Lavesson N, 2014, I C DIELECT LIQUIDS
  • [10] Fundamental property of electric field in rapeseed ester oil based on Kerr electro-optic measurement
    Nakamura, K.
    Kato, K.
    Koide, H.
    Hatta, Y.
    Okubo, H.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2006, 13 (03) : 601 - 607