共 16 条
A Study on an Operation Strategy of Dual-Infeed HVDC System
被引:1
作者:
Kim, Chan-Ki
[2
]
Jang, Gilsoo
[1
]
机构:
[1] Korea Univ, Sch Elect Engn, Seoul, South Korea
[2] KEPCO Korea Elect Power Res Inst KEPRI, Daejeon, South Korea
基金:
新加坡国家研究基金会;
关键词:
HVDC;
Multi-infeed HVDC;
Line arrester;
Voltage control;
VOLTAGE STABILITY ANALYSIS;
D O I:
10.5370/JEET.2017.12.1.045
中图分类号:
TM [电工技术];
TN [电子技术、通信技术];
学科分类号:
0808 ;
0809 ;
摘要:
This paper deals with the operation strategy of reactive power in a multi-infeed HVDC (MIHVDC) system, in which several converters are connected to the same or nearby separate AC buses. The potential problems concerning a MIHVDC system when feeding a weak AC network are as follows: the need for coordination of the recovery control, the possibility of voltage instability or low quality of the area connected to the MIHVDC system, and the risk of mutual commutation failures. These problems in MIHVDC systems are similar to those in single-infeed HVDC (SIHVDC) systems, but the differences with the phenomenon of the SIHVDC system are the interactions between converters. The main reason for the potential problems of HVDC systems (MIHVDC or SIHVDC) is voltage variation; therefore, to mitigate the voltage variations, the performances of the HVDC system should be enhanced. Consequently, to mitigate the potential problems of MIHVDC systems, several solutions are suggested in this study, including installing STATCOM and installing a line arrester on the tower. The study results will be applied to a multi-infeed HVDC system in Korea.