Lightning Impulse Corona Characteristic of 1000-kV UHV Transmission Lines and Its Influences on Lightning Overvoltage Analysis Results

被引:24
|
作者
Yang, Pengcheng [1 ]
Chen, Shuiming [1 ]
He, Jinliang [1 ]
机构
[1] Tsinghua Univ, Dept Elect Engn, State Key Lab Power Syst, Beijing 100084, Peoples R China
基金
中国国家自然科学基金;
关键词
Corona cage; electromagnetic transient calculations; impulse corona; lightning impulse; Q-V curve; ultra-high voltage (UHV) bundle conductors; CIRCUIT MODEL; PROPAGATION; TRANSIENTS; DISCHARGE; SIMULATIONS; ATTENUATION; BUNDLES; SURGES; CHARGE;
D O I
10.1109/TPWRD.2013.2278120
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The lightning overvoltage is one of key issues in designing the insulation of transmission line and power apparatus. Usually the influence of the impulse corona is ignored in numerical analysis of electromagnetic transients in power systems due to the lack of experimental data. But the relationship between the overvoltage and the insulation size of 1000-kV ac ultra-high voltage (UHV) power systems enters the nonlinear region, and a small decrease in overvoltage will lead to a high reduction in insulation size and bring huge economical benefits. So fully understanding the corona characteristics of the 1000-kV UHV transmission line is helpful to understand the actual wave process and realize a suitable insulation design of the 1000-kV UHV system. Experiments on the lightning impulse corona characteristic of bundle conductors for 1000-kV transmission lines are carried out in the China UHV ac test base and the impulse corona Q-V curves of different bundle conductors are obtained. The results show that the impulse corona leads the increment of the capacitance of the conductor. Analysis on the Q-V curves shows that the occurrence of the positive impulse corona has a time delay after the lightning impulse voltage exceeds the corona inception voltage and the delay time is a tenth of a microsecond. At the end of this paper, a simulation model for corona based on the empirical formulas of Q-V curves fitted from the test results is proposed, and is applied to the overvoltage analysis of 1000-kV transmission line and substation. The analysis results show the lightning impulse corona has a large influence on the lightning overvoltage of the transmission line and substation.
引用
收藏
页码:2518 / 2525
页数:8
相关论文
共 36 条
  • [31] Analysis of Lightning Shielding Failure for 500-kV Overhead Transmission Lines Based on an Improved Leader Progression Model
    Wei, Bengang
    Fu, Zhengcai
    Yuan, Haiyan
    IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (03) : 1433 - 1440
  • [32] Analysis of lightning-induced current and voltages on 500 kV EHV double circuit transmission lines of type DL3° andd DT 20° in lightning protection system
    Jaipradidtham, C
    TENCON 2004 - 2004 IEEE REGION 10 CONFERENCE, VOLS A-D, PROCEEDINGS: ANALOG AND DIGITAL TECHNIQUES IN ELECTRICAL ENGINEERING, 2004, : C385 - C388
  • [33] Analysis on lightning impulse type test for dry-type smoothing reactor of ± 800 kV DC Transmission Demonstration Project from Xiangjiaba to Shanghai
    Shan, Hua-Ping
    Peng, Xiao-Ying
    Wu, Jin-Ke
    Li, Jian-Jian
    Chang, Yong
    Dianwang Jishu/Power System Technology, 2010, 34 (05): : 12 - 15
  • [34] Modelling of the inhibition effect of thin-wire ultra-corona on upward leader and its application on lightning protection in high-voltage transmission lines
    Sima, Wenxia
    Fan, Shuochao
    Yang, Qing
    Yuan, Tao
    Wang, Qi
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2014, 8 (05) : 935 - 944
  • [35] Development of GIS-based Ground Flash Density and its Statistical Analysis for Lightning Performance Evaluation of Transmission Lines in Peninsular Malaysia
    Roslan, Nurzanariah
    Amirulddin, Ungku Anisa Ungku
    Kadir, Mohd Zainal Abidin Ab.
    Abdullah, Noradlina
    PERTANIKA JOURNAL OF SCIENCE AND TECHNOLOGY, 2024, 32 (01): : 395 - 418
  • [36] Calculation of Electric Field and Voltage Distribution along Glass Insulator String and Optimum Design of its Grading Rings for 1000kV a.c. UHV Transmission Lines
    Zhao, Yanzhen
    Li, Hualiang
    Ma, Xikui
    2008 WORLD AUTOMATION CONGRESS PROCEEDINGS, VOLS 1-3, 2008, : 866 - 869