On Partial Discharge/Corona Considerations for Low Voltage Switchgear and Controlgear

被引:0
|
作者
Weichert, Hans [1 ]
Benz, Pascal [1 ]
Hill, Nicholas [2 ]
Hilbert, Michael [2 ]
Kurrat, Michael [2 ]
机构
[1] Rockwell Automat Switzerland GmbH, Aarau, Switzerland
[2] Tech Univ Carolo Wilhelmina Braunschweig, Braunschweig, Germany
来源
PROCEEDINGS OF 2018 29TH INTERNATIONAL CONFERENCE ON ELECTRICAL CONTACTS AND 64TH IEEE HOLM CONFERENCE ON ELECTRICAL CONTACTS | 2018年
关键词
Partial discharge; corona; electrical field; manual motor controller; operational temperature; low voltage; variable frequency converters;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Electrical field and partial discharge (PD, corona) considerations usually are not in the foreground with low voltage switch- and control gear as per the product standards of IEC, UL and CSA. The design is mainly based on creepage and clearance dimensions, material categories described through CTI and RTI values. IEC product standards refer to the subject of insulation coordination as per the horizontal IEC 60664-family in their normative references. These standards, in principle, require PD measurements for rated voltages exceeding 500 VAC at room temperature. IEC 60664-2 gives some rules for consideration and electrical dimensioning of solid insulation. Miniaturization accompanied by increased power density and raised operational voltage as well as (non-sinusoidal) power supply generated by pulse width modulated (PWM) converters require to reconsider the relevance of electrical field stress in low voltage equipment. With variable frequency drive (VFD) fed motors reflected voltage waves were observed, causing partial discharge effects and insulation damages. Meanwhile motors and cables are available as VFD-proof versions. PD measurements on commercial manual motor controllers with sinusoidal voltages at both room temperature and a more severe elevated temperature related to the maximal operational temperature of the internal components (bimetal trip units) are presented. Conclusions are drawn and recommendations for future designs and testing are proposed.
引用
收藏
页码:246 / 253
页数:8
相关论文
共 50 条
  • [41] Partial Discharge Diagnostics for Mixed-Technology Switchgear (MTS) in Outdoor Substations
    Lopez-Roldan, J.
    Blundell, M.
    Irwin, T.
    Charlson, C.
    IEEE ELECTRICAL INSULATION MAGAZINE, 2013, 29 (03) : 41 - 47
  • [42] Partial discharge localization using time reversal: Application to gas insulated switchgear
    Zohrevand, Javad
    Karami, Hamidreza
    Rubinstein, Marcos
    Rachidi, Farhad
    ELECTRIC POWER SYSTEMS RESEARCH, 2022, 212
  • [43] Artificial Low Current Arc Fault for Pattern Recognition in Low Voltage Switchgear
    Mueller, Peter
    Tenbohlen, Stefan
    Maier, Reinhard
    Anheuser, Michael
    PROCEEDINGS OF THE FIFTY-FIFTH IEEE HOLM CONFERENCE ON ELECTRICAL CONTACTS, 2009, : 14 - +
  • [44] Corona discharge surface treater without high voltage transformer
    Burany, Nandor
    Huber, Laszlo
    Pejovic, Predrag
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2008, 23 (02) : 993 - 1002
  • [45] DC Partial Discharge Characteristics for Corona, Surface and Void Discharges
    Rahimi, M. R.
    Javadinezhad, R.
    Vakilian, Mehdi
    2015 IEEE 11TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, 2015, : 260 - 263
  • [46] Sensor Comparison for Corona Discharge Detection Under Low Pressure Conditions
    Riba, Jordi-Roger
    Gomez-Pau, Alvaro
    Moreno-Eguilaz, Manuel
    IEEE SENSORS JOURNAL, 2020, 20 (19) : 11698 - 11706
  • [47] Partial Discharge Behaviors in Cavities under Square Voltage Excitation at Very Low Frequency
    Nguyen, H. V. P.
    Phung, B. T.
    Blackburn, T.
    2016 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2016, : 866 - 869
  • [48] A Coplanar Waveguide Based Antenna for Partial Discharge Detection in Gas-insulated Switchgear
    Darwish, Ahmad
    Refaat, Shady S.
    Abu-Rub, Haitham
    Coapes, Graeme
    3RD INTERNATIONAL CONFERENCE ON SMART GRID AND RENEWABLE ENERGY (SGRE), 2022,
  • [49] Application of SCNGO-VMD-SVM in Identification of Gas Insulated Switchgear Partial Discharge
    Sun, Wei
    Ma, Hongzhong
    Wang, Sihan
    IEEE ACCESS, 2024, 12 : 43838 - 43848
  • [50] Partial discharge monitoring in medium voltage cables
    Zhou, Chengke
    Hepburn, Donald M.
    Michel, Mattheiu
    Song, Xiaodi
    Zhang, Guobin
    PROCEEDINGS OF 2008 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS, 2007, : 1021 - +