Transients in Wind Power Plants-Part I: Modeling Methodology and Validation

被引:34
作者
Badrzadeh, Babak [1 ]
Zamastil, Martin Hogdahl [2 ]
Isabegovic, Emir [3 ]
机构
[1] Vestas Technol R&D, DK-8200 Aarhus, Denmark
[2] Energinet Dk, DK-7000 Fredericia, Denmark
[3] Gothia Power, S-41133 Gothenburg, Sweden
关键词
Circuit breaker modeling; high-frequency interactions; high-frequency model validation; modeling and simulation; power system transients; temporary overvoltages (TOVs); transient overvoltages; wind power plants (WPPs); TRANSFORMERS;
D O I
10.1109/TIA.2011.2181291
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This is the first part of a two-paper series and presents the modeling methodology for all of the main components of a typical wind power plant for power system transient studies. The models developed are intended for investigation of the temporary overvoltages, switching overvoltages, and lightning overvoltages. The component models developed include the high-frequency models of the vacuum and SF6 circuit breakers, three core cables for the collector grid, and quad core cables for the wind turbine tower, turbine transformer, doubly fed asynchronous generator, and surge arrester. The models developed are wideband in nature and can be used for all studies, except the transformer model which requires two variations for the low-mid frequency range and mid-high frequency range. Detailed user-defined models developed for both vacuum and SF6 circuit breakers take account of the restrikes, reignitions, prestrikes, low-frequency high-current interruption, and high-frequency low-current interruption. The generator and transformer transient models include a representation of the various high-frequency capacitive couplings. The success criteria for each individual component model are discussed, and the model performance is validated against these criteria.
引用
收藏
页码:794 / 807
页数:14
相关论文
empty
未找到相关数据