Investigations on Single-Phasing Effect of Zigzag Autoconfigured Transformer Based 12-Pulse Rectifier

被引:0
|
作者
Kalpana, R. [1 ]
Prakash, Saravana P. [1 ]
Vidyasagar, V. S. [2 ]
Singh, Bhim [3 ]
机构
[1] NITK, Dept Elect & Elect Engn, New Delhi, India
[2] Gulbarga Elect Supply Co GESCOM, Raichur, Karnataka, India
[3] IITD, Dept Elect & Elect Engn, New Delhi, India
关键词
Active interphase reactor; front-end converter; multi-pulse rectifier; PFC; power quality; single-phasing; THD; DIODE BRIDGE RECTIFIER; MULTIPULSE RECTIFIER; HARMONIC REDUCTION; 3-PHASE;
D O I
暂无
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
High power industrial loads are often fed from front-end multi-pulse rectifier as its ability to effectively and inexpensively mitigate the harmonics on the AC side is achieved by the multi-pulse autoconfigured transformer. This paper analyzes and investigates the operability of the zigzag autoconfigured transformer based 12-pulse rectifier when one of the input terminals is open, i.e., single-phasing. Contrary to the prior art multi-pulse rectifiers, the availability of neutral point in zigzag autoconfigured transformer results in normal operation at DC side during single-phasing. A detailed MATLAB Simulation is carried out to understand the single-phasing operation of the zigzag autoconfigured transformer. Further, the experimental results from the laboratory prototype are presented to validate the simulated results.
引用
收藏
页数:6
相关论文
共 43 条
  • [31] DFT-Based Repetitive Control of a Series Active Filter Integrated With a 12-Pulse Diode Rectifier
    le Roux, Abraham D.
    Mouton, Hendrik du T.
    Akagi, Hirofumi
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2009, 24 (5-6) : 1515 - 1521
  • [32] Effect of Voltage Transformation Ratio on the Kilovoltampere Rating of Delta-Connected Autotransformer for 12-Pulse Rectifier System
    Meng, Fangang
    Yang, Wei
    Yang, Shiyan
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2013, 60 (09) : 3579 - 3588
  • [33] Effect of circulating current on input line current of 12-pulse rectifier with active inter-phase reactor
    Meng, Fangang
    Gao, Lei
    Yang, Wei
    IET POWER ELECTRONICS, 2016, 9 (07) : 1398 - 1405
  • [34] PULSE DOUBLING IN ZIGZAG-CONNECTED AUTOTRANSFORMER-BASED 12-PULSE AC-DC CONVERTER FOR POWER QUALITY IMPROVEMENT
    Abdollahi, Rohollah
    JOURNAL OF ELECTRICAL ENGINEERING-ELEKTROTECHNICKY CASOPIS, 2012, 63 (06): : 357 - 364
  • [35] Analytical Calculation of the Difference in Parallel Output Current Between the 12-pulse Rectifier Bridges Based on Transformer Leakage Inductance and DC inter-phase Reactor
    Jiang, Linfei
    Xiao, Fei
    Hu, Liangdeng
    PROCEEDINGS OF 2019 IEEE 3RD INTERNATIONAL ELECTRICAL AND ENERGY CONFERENCE (CIEEC), 2019, : 623 - 629
  • [36] Predictive Fast DSP-Based Current Controller for a 12-Pulse Hybrid-Mode Thyristor Rectifier
    Zhang Damin
    Wang Shitao
    Zhou Fengwu
    Wang Lujun
    Lu Zhengyu
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2013, 28 (11) : 5263 - 5271
  • [37] Harmonic Reduction for 12-Pulse Rectifier Using Two Auxiliary Single-Phase Full-Wave Rectifiers
    Wang, Jingfang
    Yao, Xuliang
    Gao, Xu
    Yang, Shiyan
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2020, 35 (12) : 12617 - 12622
  • [38] Double-star 12-pulse rectifier based on full-wave inter-phase reactor
    Wang J.
    Yao X.
    Feng S.
    Guan Q.
    Shen L.
    Yang S.
    1600, Electric Power Automation Equipment Press (40): : 96 - 102
  • [39] Novel hybrid 12-pulse line-interphase-transformer boost-type rectifier with controlled output voltage and sinusoidal utility currents
    Mino, Kazuaki
    Nishida, Yasuyuki
    Kolar, Johann W.
    IEEJ Transactions on Industry Applications, 2007, 127 (04) : 382 - 390
  • [40] Input Current Step-Doubling for Autotransformer-Based 12-Pulse Rectifier Using Two Auxiliary Diodes
    Wang, Jingfang
    Chen, Anchen
    Yao, Xuliang
    Guan, Qi
    Chen, Qiming
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2022, 69 (08) : 7607 - 7617