Smart load management of distribution-class toroidal transformers using a dynamic thermal model

被引:15
作者
Lu, Haowei [1 ]
Borbuev, Akim [1 ]
Jazebi, Saeed [1 ]
Hong, Tianqi [1 ]
de Leon, Francisco [1 ]
机构
[1] NYU, NYU Tandon Sch Engn, Dept Elect & Comp Engn, Brooklyn, NY 11201 USA
关键词
load management; power transformers; power distribution; thermal analysis; equivalent circuits; smart load management; distribution-class toroidal transformers; dynamic thermal model; thermal behaviour; performance assessment; life expectancy prediction; computer modelling tool; electro-thermal equivalent circuit; hot-spot temperature prediction; average surface temperatures; dry-type distribution-grade toroidal transformers; circuit components; finite-element method; POWER TRANSFORMERS; LEAKAGE INDUCTANCE; PART I; TEMPERATURES; DESIGN;
D O I
10.1049/iet-gtd.2017.0360
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Thermal behaviour is a prime factor in the accurate performance assessment of power transformers as well as in the prediction of their life expectancy. This study presents a computer modelling tool based on an electro-thermal equivalent circuit of transformers that is able to predict the hot-spot temperature and average surface temperatures for all internal layers of distribution-class toroidal transformers. Temperature is the limiting factor that prevents running transformers for hours or days in overload conditions. The modelling tool presented in this study is capable to identify the safe maximum overload current and duration that a transformer can handle without introducing damage or loss of life. The model is helpful to predict the short-term (few hours) and long-term (few days) overload capabilities of transformers. The electro-thermal model can also be used as a tool to optimise the design and evaluate the performance of transformers. This study is specifically focused on the implementation of the proposed method on dry-type distribution-grade toroidal transformers. The model is built using circuit components (lumped R and C) obtained from the thermal-electrical analogy. The model is validated with numerous finite-element method simulations and laboratory tests with transformers of various power ratings.
引用
收藏
页码:142 / 149
页数:8
相关论文
共 39 条
[31]  
Plesca A.T., 2013, INT J MATH COMPUT PH, V7, P590
[32]   Heat-Transfer Model for Toroidal Transformers [J].
Purushothaman, Sujit ;
de Leon, Francisco .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (02) :813-820
[33]   Power System State and Transmission Line Conductor Temperature Estimation [J].
Rakpenthai, Chawasak ;
Uatrongjit, Sermsak .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2017, 32 (03) :1818-1827
[34]   Improving Accuracy and Efficiency of Start-Up Cost Formulations in MIP Unit Commitment by Modeling Power Plant Temperatures [J].
Silbernagl, Matthias ;
Huber, Matthias ;
Brandenberg, Rene .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2016, 31 (04) :2578-2586
[35]   Dynamic thermal modelling of power transformers [J].
Susa, D ;
Lehtonen, M ;
Nordman, H .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (01) :197-204
[36]  
Susa D, 2006, IEEE T POWER DELIVER, V21, P1961, DOI 10.1109/TPWRD.2005.864069
[37]   A fundamental approach to transformer thermal modeling - Part I: Theory and equivalent circuit [J].
Swift, G ;
Molinski, TS ;
Lehn, W .
IEEE TRANSACTIONS ON POWER DELIVERY, 2001, 16 (02) :171-175
[38]  
Taine J., 1993, HEAT TRANSFER, P398
[39]  
Torabi M.R., 2012, P 66 SFSA TECHN OP C