Explicit Impedance Modeling and Shaping of Grid-Connected Converters via an Enhanced PLL for Stabilizing the Weak Grid Connection

被引:14
作者
Eskandari, Mohsen [1 ]
Savkin, Andrey V. V. [1 ]
Alhelou, Hassan Haes [2 ]
Blaabjerg, Frede [3 ]
机构
[1] Univ New South Wales, Sch Elect Engn & Telecommun, Sydney, NSW 2052, Australia
[2] Monash Univ, Dept Elect & Comp Syst Engn, Clayton, Vic 3800, Australia
[3] Aalborg Univ, Dept Energy Technol, DK-9220 Aalborg, Denmark
关键词
Dynamic stability; grid integration; impedance shaping; phase-locked loop (PLL); renewable energy resources (RESs); voltage source converters (VSC); and weak grid connection; VOLTAGE-SOURCE; POWER CONVERTERS; SYNCHRONIZATION; INVERTER; DESIGN; SYSTEM; VSCS;
D O I
10.1109/ACCESS.2022.3226818
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The voltage source converters (VSCs) are used to interface and control the renewable energy resources that are integrated into the power grids. However, a weak grid connection raises a stability problem for grid synchronization of the grid-feeding current-controlled VSCs (CCVSCs). This paper handles modeling and controller design for stabilizing the weak grid connection of CCVSCs. The impedance modeling/shaping of the VSC has been recognized as an effective tool to analyze and design the dynamics of the VSC. But an explicit and accurate impedance model of the CCVSC is required. Particularly, modeling the impact of the phase-locked loop (PLL) synchronization unit on the impedance model of the CCVSC is complex. Therefore, at first, an efficient impedance model of the CCVSC is developed while the impact of the PLL is rigorously considered through a complex procedure that results in an explicit/accurate impedance model. The developed impedance model is used to conduct passivity/weak grid connection stability analysis to clarify the underlying causes of instability problems. Then, a novel PLL, with an in-loop low-pass filter (LPF) to account for harmonics/asymmetries, is proposed with enhanced characteristics using the state feedback control. The impedance shaping method (with the aid of the impedance model) is utilized to design the state feedback gains. The state feedback loops provide degrees of freedom for bandwidth design of the PLL considering the current/power control loops and stabilize the system under weak grid connection/distorted conditions. Simulation results prove the accuracy and effectiveness of the models.
引用
收藏
页码:128874 / 128889
页数:16
相关论文
共 46 条
[1]   Passivity-Based Analysis and Performance Enhancement of a Vector Controlled VSC Connected to a Weak AC Grid [J].
Agbemuko, Adedotun J. ;
Dominguez-Garcia, Jose Luis ;
Gomis-Bellmunt, Oriol ;
Harnefors, Lennart .
IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (01) :156-167
[2]   Impedance and Damping Characteristics of Grid-Connected VSCs With Power Synchronization Control Strategy [J].
Alawasa, Khaled Mohammad ;
Mohamed, Yasser Abdel-Rady I. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2015, 30 (02) :952-961
[3]   Active Mitigation of Subsynchronous Interactions Between PWM Voltage-Source Converters and Power Networks [J].
Alawasa, Khaled Mohammad ;
Mohamed, Yasser Abdel-Rady Ibrahim ;
Xu, Wilsun .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2014, 29 (01) :121-134
[4]   Multivariable Droop Control of Synchronous Current Converters in Weak Grids/Microgrids With Decoupled dq-Axes Currents [J].
Ashabani, Mahdi ;
Mohamed, Yasser A. -R. I. ;
Mirsalim, Mojtaba ;
Aghashabani, Mohammad .
IEEE TRANSACTIONS ON SMART GRID, 2015, 6 (04) :1610-1620
[5]   Power-Synchronized Grid-Following Inverter Without a Phase-Locked Loop [J].
Bahrani, Behrooz .
IEEE ACCESS, 2021, 9 :112163-112176
[6]   Small-Signal Analysis of Photovoltaic Inverter With Impedance-Compensated Phase-Locked Loop in Weak Grid [J].
Berg, Matias ;
Aapro, Aapo ;
Luhtala, Roni ;
Messo, Tuomas .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2020, 35 (01) :347-355
[7]   Impedance Modeling and Analysis of Grid-Connected Voltage-Source Converters [J].
Cespedes, Mauricio ;
Sun, Jian .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2014, 29 (03) :1254-1261
[8]   Analysis of Phase-Locked Loop Low-Frequency Stability in Three-Phase Grid-Connected Power Converters Considering Impedance Interactions [J].
Dong, Dong ;
Wen, Bo ;
Boroyevich, Dushan ;
Mattavelli, Paolo ;
Xue, Yaosuo .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2015, 62 (01) :310-321
[9]   Battery energy storage systems (BESSs) and the economy-dynamics of microgrids: Review, analysis, and classification for standardization of BESSs applications [J].
Eskandari, Mohsen ;
Rajabi, Amin ;
Savkin, Andrey, V ;
Moradi, Mohammad H. ;
Dong, Zhao Yang .
JOURNAL OF ENERGY STORAGE, 2022, 55
[10]   Robust PLL Synchronization Unit for Grid-Feeding Converters in Micro/Weak Grids [J].
Eskandari, Mohsen ;
Savkin, Andrey V. V. .
IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, 2023, 19 (04) :5400-5411