Application of Multiple Resistive Superconducting Fault-Current Limiters for Fast Fault Detection in Highly Interconnected Distribution Systems

被引:28
作者
Blair, Steven M. [1 ]
Booth, Campbell D. [1 ]
Burt, Graeme M. [1 ]
Bright, Chris G. [2 ]
机构
[1] Univ Strathclyde, Dept Elect & Elect Engn, Inst Energy & Environm, Glasgow G1 1XW, Lanark, Scotland
[2] Rolls Royce Strateg Res Ctr, Elect Syst & Instrumentat Grp, Derby DE24 8BJ, England
基金
英国工程与自然科学研究理事会;
关键词
Distributed generation; fault-current limitation; low-carbon; power system protection; superconducting fault-current limiter (SFCL); CABLES; MODEL;
D O I
10.1109/TPWRD.2012.2228011
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Superconducting fault-current limiters (SFCLs) offer several benefits for electrical distribution systems, especially with increasing distributed generation and the requirements for better network reliability and efficiency. This paper examines the use of multiple SFCLs in a protection scheme to locate faulted circuits, using an approach which is radically different from typical proposed applications of fault current limitation, and also which does not require communications. The technique, referred to as "current division discrimination" (CDD), is based upon the intrinsic inverse current-time characteristics of resistive SFCLs, which ensures that only the SFCLs closest to a fault operate. CDD is especially suited to meshed networks and particularly when the network topology may change over time. Meshed networks are expensive and complex to protect using conventional methods. Simulation results with multiple SFCLs, using a thermal-electric superconductor model, confirm that CDD operates as expected. Nevertheless, CDD has limitations, which are examined in this paper. The SFCLs must be appropriately rated for the maximum system fault level, although some variation in actual fault level can be tolerated. For correct coordination between SFCLs, each bus must have at least three circuits that can supply fault current, and the SFCLs should have identical current-time characteristics.
引用
收藏
页码:1120 / 1127
页数:8
相关论文
共 35 条
[1]  
Alstom Grid, 2011, NETW PROT AUT GUID
[2]  
[Anonymous], 2011, 2422001 IEEE, DOI DOI 10.1109/IEEESTD.2001.93369
[3]  
[Anonymous], 2011, 282011 MAIB
[4]  
[Anonymous], 2010, U.K. WO/2010/015334, Patent No. 2010015334
[5]   Superconducting fault current limiter application in a power-dense marine electrical system [J].
Blair, S. M. ;
Booth, C. D. ;
Elders, I. M. ;
Singh, N. K. ;
Burt, G. M. ;
McCarthy, J. .
IET ELECTRICAL SYSTEMS IN TRANSPORTATION, 2011, 1 (03) :93-102
[6]  
Blair S.M., 2009, 2009 44 INT U POWER, P1
[7]  
Blair S. M., 2010, 10 IET INT C DEV POW
[8]   Current-Time Characteristics of Resistive Superconducting Fault Current Limiters [J].
Blair, Steven M. ;
Booth, Campbell D. ;
Burt, Graeme M. .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2012, 22 (02)
[9]   Analysis of Energy Dissipation in Resistive Superconducting Fault-Current Limiters for Optimal Power System Performance [J].
Blair, Steven M. ;
Booth, Campbell D. ;
Singh, Nand K. ;
Burt, Graeme M. ;
Bright, Chris G. .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2011, 21 (04) :3452-3457
[10]  
Booth C. D., 2008, P IMAREST B, P37