Performance evaluation of an air conditioning system based on quasi isothermal dehumidifcation

被引:14
|
作者
Jagirdar, Mrinal [1 ]
Pandelidis, Demis [2 ]
Pacak, Anna [2 ]
Worek, William [3 ]
Cetin, Sabri [4 ]
机构
[1] Eindhoven Univ Technol, Dept Chem Engn & Chem, Eindhoven, Netherlands
[2] Wroclaw Univ Sci & Technol, Dept Mech & Power Engn, 27 Wyspia Ski St, PL-50370 Wroclaw, Poland
[3] Argonne Natl Lab, 9700 S Cass Ave, Lemont, IL 60439 USA
[4] Univ Illinois, Dept Mech & Ind Engn, Chicago, IL 60607 USA
关键词
Desiccant dehumidification; Mathematical modelling; Maisotsenko cycle; Indirect evaporative cooling; Desiccant coated heat exchanger; Air conditioning; LIQUID DESICCANT DEHUMIDIFICATION; MAISOTSENKO CYCLE HEAT; MASS-TRANSFER; NUMERICAL-ANALYSIS; EXCHANGERS; COUNTER; OPTIMIZATION;
D O I
10.1016/j.enconman.2020.113009
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents a first study of novel air conditioning system based on quasi isothermal dehumidification combined with dew-point evaporative cooling through the Maisotsenko cycle (M-Cycle). The dehumidification process is realized in desiccant coated heat exchanger with heat rejection system. The key idea behind the solution is to maximize the cooling effectiveness by creating favourable conditions for dehumidification and evaporative cooling process. This is achieved by rejecting the heat of sorption in the desiccant system and providing cold and dry air for M-Cycle air cooler, which allows the system to be powered by using low-grade heat energy at 50 degrees C. The analysis is performed on the basis of experimentally validated numerical models of each component combined in a unified model of the system. The goal of the study is to determine the performance of the solution under different operational conditions. In addition two types of M-Cycle air coolers (i.e. cross-flow and regenerative unit) are compared to establish which unit is more suitable as the source of cooling energy for the system. It was established that proposed system is able to provide comfortable room parameters (supply air temperature equal 17 degrees C and humidity ratio equal 0.010 kg/kg-da) for outdoor air temperatures ranging from 28 to 36 degrees C and outdoor air humidity ranging from 0.010 to 0.018 kg/kg-da. This means that the proposed solution is able to provide comfortable conditions in temperate and humid climates. Results also indicate that the system consisting of the regenerative M-Cycle HMX allows better cooling load management, offers higher thermal Coefficient of Performance (COPth) and uses less water compared to the system with the cross-flow HMX. However, the system with cross-flow heat and mass exchanger (HMX) has a relatively greater electrical Coefficient of Performance (COPel) in most cases.
引用
收藏
页数:25
相关论文
共 50 条
  • [11] Energy performance evaluation and application of an air treatment system for conditioning building spaces in tropics
    Cui, X.
    Mohan, B.
    Islam, M. R.
    Chou, S. K.
    Chua, K. J.
    APPLIED ENERGY, 2017, 204 : 1500 - 1512
  • [12] Performance evaluation of a variable frequency heat pump air conditioning system for electric bus
    Peng, Qinghong
    Du, Qungui
    International Journal of Fluid Machinery and Systems, 2015, 8 (01) : 13 - 22
  • [13] Thermal performance of desiccant-based solar air-conditioning system with silica gel coating
    Nain, Sunil
    Kajal, Sanjay
    Parinam, Anuradha
    ENVIRONMENT DEVELOPMENT AND SUSTAINABILITY, 2020, 22 (01) : 281 - 296
  • [14] Performance analysis of a novel liquid desiccant evaporative cooling fresh air conditioning system with solution recirculation
    Zhang, Fan
    Yin, Yonggao
    Zhang, Xiaosong
    BUILDING AND ENVIRONMENT, 2017, 117 : 218 - 229
  • [15] Performance analysis and simulation of automobile air conditioning system
    Lee, GH
    Yoo, JY
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2000, 23 (03): : 243 - 254
  • [16] Energy Performance of a Novel Hybrid Air Conditioning System Built on Gravity-Assisted Heat Pipe-Based Indirect Evaporative Cooler
    Rajski, Krzysztof
    Sohani, Ali
    Jafari, Sina
    Danielewicz, Jan
    Sayegh, Marderos Ara
    ENERGIES, 2022, 15 (07)
  • [17] Performance study of desiccant coated heat exchanger air conditioning system in winter
    Ge, T. S.
    Dai, Y. J.
    Wang, R. Z.
    ENERGY CONVERSION AND MANAGEMENT, 2016, 123 : 559 - 568
  • [18] Performance study of a novel indirect evaporative/air-cooled thermoelectric cooling air conditioning system
    Duan, Yujie
    Zhou, Yuanyuan
    Dou, Zhongyu
    Dai, Qiumin
    Yu, Yanshun
    Li, Qiang
    BUILDING AND ENVIRONMENT, 2024, 265
  • [19] Energy Performance Evaluation of an Air-Conditioning System in a Large Scale Office Building by Commissioning
    Zhang, Weijie
    Liu, Jiuling
    Jia, Jieqing
    6TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS I-III, PROCEEDINGS, 2009, : 351 - 358
  • [20] Experiments and modeling on thermal performance evaluation of standalone and M-cycle based desiccant air-conditioning systems
    Bhat, Showkat Ahmad
    Sajjad, Uzair
    Hussain, Imtiyaz
    Yan, Wei-Mon
    Raza, Hafiz M. U.
    Ali, Hafiz Muhammad
    Sultan, Muhammad
    Omar, Hani
    Azam, Muhammad Waheed
    Bozzoli, Fabio
    Huang, Nen-Fu
    ENERGY REPORTS, 2024, 11 : 1445 - 1454