Experimental investigation on water quality standard of Yangtze River water source heat pump

被引:3
作者
Qin, Zenghu [1 ]
Tong, Mingwei [1 ]
Kun, Lin [2 ]
机构
[1] Chongqing Univ, Minist Educ, Key Lab Low Grade Energy Utilizat Technol & Syst, Chongqing 400030, Peoples R China
[2] Guangdong Chigo Air Conditioner Co Ltd, Guangzhou 528244, Guangdong, Peoples R China
关键词
coefficient of performance; fouling resistance; heat capacity; water quality; Yangtze River water heat pump; AIR-CONDITIONING SYSTEM; INDEX;
D O I
10.2166/wst.2012.294
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Due to the surface water in the upper reaches of Yangtze River in China containing large amounts of silt and algae, high content of microorganisms and suspended solids, the water in Yangtze River cannot be used for cooling a heat pump directly. In this paper, the possibility of using Yangtze River, which goes through Chongqing, a city in southwest China, as a heat source-sink was investigated. Water temperature and quality of the Yangtze River in the Chongqing area were analyzed and the performance of water source heat pump units in different sediment concentrations, turbidity and algae material conditions were tested experimentally, and the water quality standards, in particular surface water conditions, in the Yangtze River region that adapt to energy-efficient heat pumps were also proposed. The experimental results show that the coefficient of performance heat pump falls by 3.73% to the greatest extent, and the fouling resistance of cooling water in the heat exchanger increases up to 25.6% in different water conditions. When the sediment concentration and the turbidity in the river water are no more than 100 g/m(3) and 50 NTU respectively, the performance of the heat pump is better, which can be used as a suitable river water quality standard for river water source heat pumps.
引用
收藏
页码:1103 / 1109
页数:7
相关论文
共 13 条
  • [1] Water quality characteristics of Densu River basin in south-east Ghana
    Amoako, J.
    Karikari, A. Y.
    Ansa-Asare, O. D.
    Adu-Ofori, E.
    [J]. WATER SCIENCE AND TECHNOLOGY, 2010, 61 (06) : 1467 - 1477
  • [2] Annamaria B., 2012, APPL ENERG, V91, P222
  • [3] Application of water quality index for assessment of surface water quality surrounding integrated industrial estate-Pantnagar
    Banerjee, Tirthankar
    Srivastava, Rajeev Kumar
    [J]. WATER SCIENCE AND TECHNOLOGY, 2009, 60 (08) : 2041 - 2053
  • [4] Experimental investigation of Seyhan River and dam lake as heat source-sink for a heat pump
    Büyükalaca, O
    Ekinci, F
    Yilmaz, T
    [J]. ENERGY, 2003, 28 (02) : 157 - 169
  • [5] Underground water-source loop heat-pump air-conditioning system applied in a residential building in Beijing
    Chen, C
    Sun, FL
    Feng, L
    Liu, M
    [J]. APPLIED ENERGY, 2005, 82 (04) : 331 - 344
  • [6] A raw water source heat pump air-conditioning system
    Cho, Yong
    Yun, Rin
    [J]. ENERGY AND BUILDINGS, 2011, 43 (11) : 3068 - 3073
  • [7] Henderson H.I., 2000, ASHRAE Transactions, V106, P533
  • [8] Koo K., 2007, P C SOC AIR COND REF, P788
  • [9] Ma G. Y., 2002, HEATING VENTILATING, V32, P130
  • [10] Development of dual-source hybrid heat pump system using groundwater and air
    Nam, Yujin
    Ooka, Ryozo
    Shiba, Yoshiro
    [J]. ENERGY AND BUILDINGS, 2010, 42 (06) : 909 - 916