Challenges in predicting steam-side pressure drop and heat transfer in air-cooled power plant condensers

被引:23
作者
Mahvi, Allison J. [1 ]
Rattner, Alexander S. [1 ]
Lin, Jennifer [1 ]
Garimella, Srinivas [1 ]
机构
[1] Georgia Inst Technol, George W Woodruff Sch Mech Engn, Sustainable Thermal Syst Lab, Atlanta, GA 30332 USA
基金
美国国家科学基金会;
关键词
Steam condensation; Air-cooled condenser; Power plant; Water conservation; MICRO-FIN TUBES; FILM CONDENSATION; 2-PHASE FLOW; THERMODYNAMIC PERFORMANCE; GENERAL CORRELATION; ENHANCED TUBES; PART II; SMOOTH; PIPES; OPTIMIZATION;
D O I
10.1016/j.applthermaleng.2018.01.008
中图分类号
O414.1 [热力学];
学科分类号
摘要
Conventional power plant condensers operate at unsustainably high cooling water consumption rates (228 m(3) MW h(-1)). Dry air-cooled condensers (ACCs) can enable reduced water consumption in power plants. However, ACCs are rarely employed because of the substantial decreases in condenser performance and power plant efficiencies compared to wet-cooled systems. ACC studies typically focus on air-side transport, assuming that the effects of steam-side pressure drop and thermal resistance are small. The objective of the present investigation is to scrutinize this assumption - quantifying the influence of steam-side effects on ACC operation. A detailed model of a representative ACC is formulated. Model results demonstrate that condensation heat transfer and pressure drop are poorly characterized at ACC operating conditions. Predicted power plant efficiency varies by 0.7% with different condensation heat transfer models. Additionally, predicted plant efficiencies vary depending on which pressure drop correlation is employed. The differences are exacerbated at low steam saturation pressures (similar to 4 kPa), where the cycle efficiencies range from 36.0% and 37.7% between different pressure drop correlations. Results from this study indicate that both steam side and air-side effects must be considered to improve ACC performance. Some methods for enhancing in-tube condensation are mentioned, and future ACC research needs are discussed. (C) 2018 Elsevier Ltd. All rights reserved.
引用
收藏
页码:396 / 406
页数:11
相关论文
共 24 条
  • [21] Reduced order analysis of flow and heat transfer for air-cooled condenser of power generating unit
    Du, Xiaoze
    Hu, Hemin
    Shen, Yinqi
    Yang, Lijun
    Yang, Yongping
    APPLIED THERMAL ENGINEERING, 2013, 51 (1-2) : 383 - 392
  • [22] Air-side heat transfer and pressure drop characteristics of accelerated flow evaporators
    Waltrich, Paulo J.
    Barbosa, Jader R., Jr.
    Hermes, Christian J. L.
    Melo, Claudio
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (02): : 484 - 497
  • [23] A study of the air-side heat transfer and pressure drop characteristics of tube-fin 'no-frost' evaporators
    Barbosa, Jader R., Jr.
    Melo, Claudio
    Hermes, Christian J. L.
    Waltrich, Paulo J.
    APPLIED ENERGY, 2009, 86 (09) : 1484 - 1491
  • [24] Modeling of air-side heat transfer and pressure drop of straight fin-tube no-frost evaporators for a household refrigerator
    Choi, Bong-Jun
    Jeong, Ji Hwan
    JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY, 2020, 34 (11) : 4773 - 4784