CFD research on runaway transient of pumped storage power station caused by pumping power failure

被引:25
作者
Zhang, L. G. [1 ]
Zhou, D. Q. [1 ]
机构
[1] Hohai Univ, Coll Energy & Elect, Nanjing, Jiangsu, Peoples R China
来源
6TH INTERNATIONAL CONFERENCE ON PUMPS AND FANS WITH COMPRESSORS AND WIND TURBINES (ICPF2013) | 2013年 / 52卷
关键词
D O I
10.1088/1757-899X/52/5/052027
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
To study runaway transient of pumped storage power station caused by pumping power failure, three dimensional unsteady numerical simulations were executed on geometrical model of the whole flow system. Through numerical calculation, the changeable flow configuration and variation law of some parameters such as unit rotate speed, flow rate and static pressure of measurement points were obtained and compared with experimental data. Numerical results show that runaway speed agrees well with experimental date and its error was 3.7%. The unit undergoes pump condition, brake condition, turbine condition and runaway condition with flow characteristic changing violently. In runaway condition, static pressure in passage pulses very strongly which frequency is related to runaway speed.
引用
收藏
页数:7
相关论文
共 5 条
[1]  
Huang W.D., 2012, P 26 IAHR S HYDR MAC
[2]  
[李金伟 LI Jinwei], 2008, [水力发电学报, Journal of Hydroelectric Engineering], V27, P148
[3]  
Nicolle J., 2012, P 26 IAHR S HYDR MAC
[4]   Evaluation of Statistical Rainfall Disaggregation Methods Using Rain-Gauge Information for West-Central Florida [J].
Zhang, Jing ;
Murch, Renee R. ;
Ross, Mark A. ;
Ganguly, Auroop R. ;
Nachabe, Mahmood .
JOURNAL OF HYDROLOGIC ENGINEERING, 2008, 13 (12) :1158-1169
[5]  
Zhou Da-qing, 2013, Journal of Sichuan University (Engineering Science Edition), V45, P63