Feasibility and performance study of the hybrid ground-source heat pump system for one office building in Chinese heating dominated areas

被引:202
作者
Liu, Zhijian [1 ]
Xu, Wei [2 ]
Zhai, Xue [1 ]
Qian, Cheng [2 ]
Chen, Xi [2 ]
机构
[1] North China Elect Power Univ, Dept Power Engn, Baoding 071003, Hebei, Peoples R China
[2] China Acad Bldg Res, China Inst Bldg Environm & Energy, Beijing 100013, Peoples R China
关键词
Hybrid ground source heat pump (HGSHP); Auxiliary heat source; Ground source heat pump (GSHP); Cold climate zone; Soil cold buildup; COLD REGIONS; OPERATION; OPTIMIZATION; STRATEGIES; EFFICIENCY; CLIMATE; DESIGN;
D O I
10.1016/j.renene.2016.10.006
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Most buildings in the cold climate zone have unbalanced loads, mainly dominated by heating loads. The cold buildup within the soil would definitely reduce the soil temperature, which could consequently disturb the soil temperature balance, and furthermore, deteriorate the performance of ground source heat pump. A hybrid ground-source heat pump (HGSHP) with auxiliary heat source could be proposed to solve this problem. The paper aimed at investigating the feasibility and performance of HGSHP in Shenyang located in the cold area. Firstly, hourly dynamic loads of one office building were calculated. Then, three systems, including one HGSHP system with boiler as auxiliary heat source, ground source heat pump system (GSHP), and a traditional electric water chiller + boiler system (WB) were designed and simulated for this office building by TRNSYS. Several performance parameters for these three systems were obtained. These parameters included the hourly outlet/inlet temperature of buried pipes, hourly soil temperature, energy consumption distribution and the coefficient of performance (COP). Simulation results indicated that HGSHP system with boiler as auxiliary heat source could effectively solve cold accumulation problem and reduce traditional energy consumption. These results could provide some reference on HGSHP system utilization in the cold climate zones of China. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1131 / 1140
页数:10
相关论文
共 30 条
[1]   A spectral model for transient heat flow in a double U-tube geothermal heat pump system [J].
Al-Khoury, Rafid ;
Focaccia, Sara .
RENEWABLE ENERGY, 2016, 85 :195-205
[2]   A methodology and computerized approach for optimizing hybrid ground source heat pump system design [J].
Alavy, Masih ;
Nguyen, Hiep V. ;
Leong, Wey H. ;
Dworkin, Seth B. .
RENEWABLE ENERGY, 2013, 57 :404-412
[3]   Hybrid ground-source heat pump system with active air source regeneration [J].
Allaerts, K. ;
Coomans, M. ;
Salenbien, R. .
ENERGY CONVERSION AND MANAGEMENT, 2015, 90 :230-237
[4]  
[Anonymous], 2005, GB501892005 BEIJ MIN
[5]  
Beijing Ministry of Construction of the People's Republic of China, 2015, GB503662015 BEIJ MIN
[6]   Evaluation of ground-source heat pump combined latent heat storage system performance in greenhouse heating [J].
Benli, Hueseyin ;
Durmus, Aydin .
ENERGY AND BUILDINGS, 2009, 41 (02) :220-228
[7]   Optimization of design and operation parameters for hybrid ground-source heat pump assisted with cooling tower [J].
Cui, Wenzhi ;
Zhou, Shiyu ;
Liu, Xiangyang .
ENERGY AND BUILDINGS, 2015, 99 :253-262
[8]   Thermal performance and operation strategy optimization for a practical hybrid ground-source heat-pump system [J].
Fan, Rui ;
Gao, Yan ;
Hua, Li ;
Deng, Xiaoxi ;
Shi, Jie .
ENERGY AND BUILDINGS, 2014, 78 :238-247
[9]   Performance analysis of hybrid ground source heat pump systems based on ANN predictive control [J].
Gang, Wenjie ;
Wang, Jinbo ;
Wang, Shengwei .
APPLIED ENERGY, 2014, 136 :1138-1144
[10]   Regional application of ground source heat pump in China: A case of Shenyang [J].
Geng, Yong ;
Sarkis, Joseph ;
Wang, Xinbei ;
Zhao, Hongyan ;
Zhong, Yongguang .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2013, 18 :95-102