Moisture transfer characteristics of a LiCl-impregnated paper membrane used for an enthalpy exchanger

被引:12
作者
Lee, Eul-Jong [1 ]
Lee, Jung-Pyo [1 ]
Kim, Nae-Hyun [1 ]
机构
[1] Univ Incheon, Sch Mech Syst Engn, Inchon 406772, South Korea
基金
新加坡国家研究基金会;
关键词
LiCl-impregnated paper; Enthalpy exchanger; Diffusion coefficient; Moisture permeability; ENERGY WHEEL EFFECTIVENESS; MASS-TRANSFER; WATER TRANSPORT; PART I; HEAT; VAPOR; PERFORMANCE; PERMEATION; DIFFUSION; PLATE;
D O I
10.1007/s12206-013-0333-2
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
In this study, moisture diffusion coefficient of a LiCl-impregnated paper membrane was experimentally obtained through an analysis of heat and moisture transfer of an enthalpy exchanger made with the membrane. A sorption curve was separately obtained by a weighing method. Tests were conducted as a function of relative humidity and temperature. Diffusion coefficient first increases up to 60% relative humidity and then decreases. It also increases with the increase of temperature. The variation of the diffusion coefficient is in the range of 1.8 x 10(-11) m(2)/s to 6.0 x 10(-11) m(2)/s, which is smaller than reported values of hydrophilic polymers. The variation of the moisture permeability, however, is in the range of 2.4 x 10(-7) kg/ms to 1.2 x 10(-6) kg/ms, which is comparable with reported values of hydrophilic polymers. Thus, similar moisture transfer performance is expected between LiCl-impregnated paper and polymer enthalpy exchangers. Possible explanation on the behavior of the diffusion coefficient with relative humidity is provided.
引用
收藏
页码:1527 / 1537
页数:11
相关论文
共 45 条