Instability of the continuously transposed cable under axial short-circuit forces in transformers

被引:19
作者
Patel, MR [1 ]
机构
[1] US Merchant Marine Acad, Kings Point, NY 11024 USA
关键词
axial compression; coil; instability; mechanical strength; short-circuit force; tilting; transformer;
D O I
10.1109/61.974202
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The axial instability of the winding conductor is one of the principal modes of mechanical failure in large power transformers. It is caused by axial compressive forces generated by the electromagnetic interaction of the short-circuit current and the radial leakage flux. It is a buckling type of mechanical instability that occurs under compression. Two possible modes of failure in the layer type coil wound with the continuously transposed cable are identified and analyzed in this paper. The critical design loads leading to instability of the individual strands as well as of the whole cable are separately derived. The actual instability threshold of the coil would be the lesser of the two critical loads. For the through-fault integrity of the transformer design, this threshold must be greater than the peak compressive force on the cable under the worst case short-circuit current.
引用
收藏
页码:149 / 154
页数:6
相关论文
共 7 条
[1]  
[Anonymous], 142 CIGRE
[2]  
[Anonymous], P IEE C
[3]   DYNAMIC-RESPONSE OF POWER TRANSFORMERS UNDER AXIAL SHORT-CIRCUIT FORCES .1. WINDING AND CLAMP AS INDIVIDUAL COMPONENTS [J].
PATEL, MR .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1973, PA92 (05) :1558-1566
[4]  
PATEL MR, 1973, IEEE T POWER APP SYS, V92, P1559
[5]  
TIMOSHENKO SP, STRENGTH MAT, V1
[6]  
TIMOSHENKO SP, STRENGTH MAT, V2
[7]  
WATERS M, 1996, SHORT CIRCUIT STRENG, P103