SOFC Detector for Portable Gas Chromatography: High-sensitivity Detection of Dissolved Gases in Transformer Oil

被引:31
作者
Fan, Jingmin [1 ]
Wang, Feng [1 ]
Sun, Qiuqin [1 ]
Bin, Feng [1 ]
Ding, Jiafeng [2 ]
Ye, Huisheng [3 ]
机构
[1] Hunan Univ, Coll Elect & Informat Engn, Changsha 410082, Hunan, Peoples R China
[2] Cent South Univ, Sch Phys & Elect, Changsha 410083, Peoples R China
[3] Hunan Elect Power Corp Res Inst, State Grid, Changsha 410007, Hunan, Peoples R China
基金
中国国家自然科学基金;
关键词
Power transformer; Gas detectors; Chromatography; Oil insulation; Fuel cells; FAULT-DIAGNOSIS; APPARATUS;
D O I
10.1109/TDEI.2017.006438
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Dissolved gas analysis (DGA) is widely used in diagnosing the incipient faults of power transformer. The detector is the key component for this method. Despite various sensors for DGA application, many of them suffer from poor stability and low sensitivity. A solid oxide fuel cell (SOFC) detector is designed in this paper to address these problems. The mechanism of the detector is briefly introduced, and it is fabricated in a mold. The test process is elucidated. For calibration purpose, two mathematical models of the detector, i.e., double-logarithmic model (DLM) and linearity model (LM), are compared with each other. Experimental results demonstrate that the SOFC detector exhibits good repeatability at given concentrations and excellent linearity with DLM. The results indicate that accurate and high-precision measurement of H-2, CH4, CO, C2H4, C2H6, and C2H2 can be achieved using the SOFC detector and the proposed DLM.
引用
收藏
页码:2854 / 2863
页数:10
相关论文
共 22 条
[21]   Distribution-Based Classification Method for Baseline Correction of Metabolomic 1D Proton Nuclear Magnetic Resonance Spectra [J].
Wang, Kuo-Ching ;
Wang, San-Yuan ;
Kuo, Ching-hua ;
Tseng, Yufeng J. .
ANALYTICAL CHEMISTRY, 2013, 85 (02) :1231-1239
[22]  
Zhao AX, 2014, IEEE IMTC P, P1036, DOI 10.1109/I2MTC.2014.6860900