CFD Design and Validation of a Thermal Storage Tank System and Its Impact in a Design-Build Project

被引:0
作者
Ghias, Reza [1 ,2 ]
Kilkeary, Michael [2 ]
机构
[1] ASC, Dulles, VA 20166 USA
[2] Southland Ind, Dulles, VA 20166 USA
来源
2016 ASHRAE WINTER CONFERENCE PAPERS | 2016年
关键词
FLOW;
D O I
暂无
中图分类号
O414.1 [热力学];
学科分类号
摘要
The use of advanced engineering tools in HVAC industry has increased as the cost of computational fluid dynamics (CFD) has become more affordable for engineering firms. A thermal storage tank system utilized a series of vertical tanks to store chilled water and supplement chillers in the event of a power failure. Chilled water is routed from the storage tanks to critical equipment during chiller re-start, bridging the gap in time that the chillers are unable to provide set-point chilled water due to power failure and subsequent required time to re-start. The main challenge of the tank sizing was to optimize the tanks in order to maximize the output time of stored chilled water while minimizing the height and quantity of the tanks. The goal was achieved through an innovative design in which the tank diffusers were designed through a series of simulations. Once installed, the system was tested rigorously to the same conditions that were previously simulated during design. The result of field-testing verified that the CFD model was accurate within two percent margin of error. Utilization of this process allowed the design-build team to save installation time, money, materials, and building square footage by reducing the number of required storage tanks to provide the required stored chilled water quantity.
引用
收藏
页数:8
相关论文
共 12 条
[1]  
[Anonymous], FLUENT MAN R14
[2]   Measured and modeled charging of a stratified chilled water thermal storage tank with slotted pipe diffusers [J].
Bahnfleth, WP ;
Song, J ;
Cimbala, JM .
HVAC&R RESEARCH, 2003, 9 (04) :467-491
[3]  
DORGAN CE, 1994, ASHRAE J, V36, P8
[4]   NUMERICAL-SIMULATION OF STRATIFICATION BEHAVIOR IN THERMAL STORAGE TANKS [J].
GHADDAR, NK ;
ALMARAFIE, AM ;
ALKANDARI, A .
APPLIED ENERGY, 1989, 32 (03) :225-239
[5]  
Ghias R., 2013, DE13C046 ASHRAE
[6]   Model of the transient stratified flow into a chilled-water storage tank [J].
Homan, KO ;
Soo, SL .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1997, 40 (18) :4367-4377
[7]  
HUDSON HE, 1979, J ENV ENG DIV-ASCE, V105, P745
[8]  
Karim A., 2009, WORLD ACAD SCI ENG T, V53, P326
[9]  
Stewart W.E., 1992, ASHRAE Transactions, V206, P131
[10]  
Yoo J., 1986, ASHRAE T, V92, P280