Impact of High Voltage Harmonics on Interpretation of Partial Discharge Patterns

被引:48
作者
Florkowski, Marek [1 ]
Florkowska, Barbara [2 ]
Furgal, Jakub [2 ]
Zydron, Pawel [2 ]
机构
[1] ABB Corp Res, PL-31038 Krakow, Poland
[2] AGH Univ Sci & Technol, Dept Elect & Power Engn, PL-30059 Krakow, Poland
关键词
Harmonics; partial discharges; diagnostics; transformer; windings; TRANSFORMER; OIL;
D O I
10.1109/TDEI.2013.6678848
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Typically, in laboratory and diagnostics tests focused on measuring partial discharges, a pure sinusoidal voltage waveform is assumed. However, in practice the spectral content of the applied voltage is rarely so ideal and additional spectral components have a significant impact on the discharge behavior in electrical insulation systems. In this paper the influence of voltage harmonics on partial discharge behavior and pattern evolution is analyzed. The presented experiments were conducted on a transformer installed in a municipal network and on specimens representing defects in a transformer insulation system, in the form of a micro blade protrusion on a winding conductor and an embedded gas inclusion. The experimental results showed that various harmonic compositions superimposed on the fundamental sinusoidal waveform have a significant impact on PD intensity and maximum charge. In consequence, PD pattern phase and amplitude distributions are distorted and calculated statistical parameters are changed. The rough parameters reflecting the waveform spectral quality, such as THD, are rather superficial and do not provide a unique and reliable signature of the applied voltage in terms of phase angle variations. In certain environments, neglecting harmonic content in the voltage may lead to a misleading interpretation and assessment of partial discharge severity. A complete knowledge of harmonic content is essential and critical in conducting a proper assessment of the impact of PD, including acceptability criteria and compatibility with the standards.
引用
收藏
页码:2009 / 2016
页数:8
相关论文
共 25 条
  • [1] [Anonymous], 5 INT C PROP APPL DI
  • [2] [Anonymous], 1992, 5191992 IEEE
  • [3] [Anonymous], P5191D12 IEEE
  • [4] Investigating the Impact of Harmonics on the Breakdown of Epoxy Resin through Electrical Tree Growth
    Bahadoorsingh, S.
    Rowland, S. M.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (05) : 1576 - 1584
  • [5] Bahadoorsingh S., 2010, 2010 10 IEEE INT C S, P1
  • [6] Identifying Harmonic Attributes From Online Partial Discharge Data
    Catterson, Victoria M.
    Bahadoorsingh, Sanjay
    Rudd, Susan
    McArthur, Stephen D. J.
    Rowland, Simon M.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (03) : 1811 - 1819
  • [7] Duarte LHS, 2002, INT C HARMON QUAL PO, P334
  • [8] Emanuel AE, 2002, INT C HARMON QUAL PO, P788
  • [9] The effect of voltage distortion on ageing acceleration of insulation systems under partial discharge activity
    Fabiani, D
    Montanari, GC
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2001, 17 (03) : 24 - 33
  • [10] Florkowska B., 2012, IMPACT FAST TRANSIEN