Comparison of Three Active-Frequency-Drift Islanding Detection Methods for Single-Phase Grid-Connected Inverters

被引:0
作者
Kan, Jia-rong [1 ]
Jiang, Hui [1 ]
Tang, Yu [2 ]
Wu, Dong-chun [1 ]
Wu, Yun-ya [1 ]
Wu, Jiang [3 ]
机构
[1] Yancheng Inst Technol, Dept Elect Engn, Yancheng, Peoples R China
[2] Hebei Univ Technol, Dept Elect Engn, Tianjin, Peoples R China
[3] Natl Grid Jiangsu Elect Power Co, Suzhou Power Supply Co, Suzhou, Peoples R China
关键词
FD-PLL; IDM; NDZ error; Power quality; SFS; Single-phase grid-connected inverter (SPGCI); SMS; DISTRIBUTED GENERATION; POWER-CONTROL; PERFORMANCE; STRATEGY;
D O I
10.6113/JPE.2019.19.2.509
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A novel islanding detection method is proposed in this paper. It is based on a frequency drooping PLL, which was presented in a previous work. The cause of errors in the non-detection zone (NDZ) of conventional frequency disturbance islanding detection methods (IDM) is analyzed. A frequency drooping phase-locked-loop (FD-PLL) is introduced into a single-phase grid-connected inverter (SPGCI), which can guarantee that grid current is in phase with the grid voltage. A novel FD-PLL IDM is proposed by improving this PLL. In order to verify the performance of the proposed FD-PLL IDM, a full performance comparison between the proposed IDM and typical existing active frequency drift IDMs is carried out, which includes both dynamic performance and steady performance. With the same NDZ, the total harmonic distortion of the grid-current in the dynamic process and steady state is analyzed. The proposed FD-PLL IDM, regardless of the dynamic or steady process, has the best power quality. Experimental and simulation results verify that the proposed FD-PLL IDM has excellent performance.
引用
收藏
页码:509 / 518
页数:10
相关论文
共 22 条
  • [1] Frequency fuzzy anti-islanding for grid-connected and islanding operation in distributed generation systems
    Aguiar, Cassius R.
    Bastos, Renan F.
    Goncalves, Amilcar F. Q.
    Neves, Rodolpho V. A.
    Reis, Giann B.
    Machado, Ricardo Q.
    [J]. IET POWER ELECTRONICS, 2015, 8 (07) : 1255 - 1262
  • [2] [Anonymous], 2002, 9292000 IEEE
  • [3] [Anonymous], 154712005 IEEE
  • [4] Active Islanding Detection for Inverter-Based Distributed Generation Systems With Power Control Interface
    Geng, Hua
    Xu, Dewei
    Wu, Bin
    Yang, Geng
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 2011, 26 (04) : 1063 - 1072
  • [5] Hou C., 1996, IET POWER ELECTRON, V6, P1658
  • [6] Jia-rong Kan, 2012, Proceedings of the 2012 IEEE 7th International Power Electronics and Motion Control Conference (ECCE 2012), P2183, DOI 10.1109/IPEMC.2012.6259184
  • [7] Kaiser DA, 2012, IEEE ENER CONV, P930, DOI 10.1109/ECCE.2012.6342719
  • [8] Advanced Islanding Detection Functionality for Future Electricity Distribution Networks
    Laaksonen, H.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (04) : 2056 - 2064
  • [9] Improvement on Stability and Islanding Detection Performances by Advanced Inverter Control of DG
    Lee, Soo Hyoung
    Park, Jung-Wook
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2013, 28 (04) : 3954 - 3963
  • [10] New Islanding Detection Method for Inverter-Based Distributed Generation Considering Its Switching Frequency
    Lee, Soo-Hyoung
    Park, Jung-Wook
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2010, 46 (05) : 2089 - 2098