Partial discharge study in transformer oil due to particle movement under DC voltage using the UHF technique

被引:52
作者
Sarathi, R. [1 ]
Reid, A. J. [1 ]
Judd, M. D. [1 ]
机构
[1] Univ Strathclyde, Dept Elect & Elect Engn, Inst Energy & Environm, Glasgow G1 1XQ, Lanark, Scotland
关键词
partial discharges; UHF sensors; transformer oil; converter transformers; insulation; condition monitoring;
D O I
10.1016/j.epsr.2008.03.022
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Converter transformers are one of the key components in high voltage DC power networks. The insulation of these transformers is stressed by both AC and DC voltages. Therefore, AC and DC voltage tests are routinely applied during factory tests to verify the performance of the insulation structure. Partial discharges in an insulation system are incipient discharges that can damage materials and may eventually lead to complete failure of the insulation system during operation. Recently it has been shown that monitoring such discharges formed under AC stress is feasible using Ultra High Frequency (UHF) measurement technique and that there is a reasonable correlation between the partial discharge magnitude and the amplitude of the UHF signal generated by partial discharges. However,the partial discharge activity under DC voltages is not fully understood. This paper describes a study using the UHF technique to improve our understanding of particle-induced partial discharge activity under DC voltages in mineral oil insulation. UHF signals generated due to conducting particle contamination in transformer oil under AC and DC voltages are compared and analyzed. A method for distinguishing particle discharges in regions of high or low electric field stress is proposed based on frequency-domain analysis of the measured UHF signal. (C) 2008 Elsevier B.V. All rights reserved.
引用
收藏
页码:1819 / 1825
页数:7
相关论文
共 24 条
[2]  
[Anonymous], 2000, IECStd.60270
[3]   Propagation and structure of streamers in liquid dielectrics [J].
Beroual, A ;
Zahn, M ;
Badent, A ;
Kist, K ;
Schwabe, AJ ;
Yamashita, H ;
Yamazawa, K ;
Danikas, M ;
Chadband, WG ;
Torshin, Y .
IEEE ELECTRICAL INSULATION MAGAZINE, 1998, 14 (02) :6-17
[4]   THE MOVEMENT OF A CONDUCTING PARTICLE IN TRANSFORMER OIL IN AC FIELDS [J].
BIRLASEKARAN, S .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1993, 28 (01) :9-17
[5]   THE MEASUREMENT OF CHARGE ON SINGLE PARTICLES IN TRANSFORMER OIL [J].
BIRLASEKARAN, S .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1991, 26 (06) :1094-1103
[6]   Particle-initiated breakdown in a quasi-uniform field in transformer oil [J].
Carraz, F ;
Rain, P ;
Tobazeon, R .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1995, 2 (06) :1052-1063
[7]  
Cavallini A, 2005, ICDL: 2005 IEEE International Conference on Dielectric Liquids, P241
[8]   UHF and current pulse measurements of partial discharge activity in mineral oil [J].
Cleary, GP ;
Judd, MD .
IEE PROCEEDINGS-SCIENCE MEASUREMENT AND TECHNOLOGY, 2006, 153 (02) :47-54
[9]  
CONVERY A, 2003, P 13 INT S HIGH VOLT
[10]   Modeling of conductive particle behavior in insulating fluids affected by DC electric fields [J].
Dascalescu, L ;
Mihailescu, M ;
Tobazeon, R .