Measurement and simulation of partial discharge in oil-paper insulation under the combined AC-DC voltage

被引:19
作者
Sha, Yanchao [1 ]
Zhou, Yuanxiang [1 ]
Zhang, Ling [1 ]
Huang, Meng [1 ]
Jin, Fubao [1 ]
机构
[1] Tsinghua Univ, Dept Elect Engn, State Key Lab Power Syst, Beijing 100084, Peoples R China
关键词
Combined AC-DC voltage; Oil-paper insulation; Partial discharge inception characteristics; Streamer process; TRANSFORMER OIL; PROPAGATION; GENERATION; LIQUID; FIELD;
D O I
10.1016/j.elstat.2012.11.013
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Depending on unique operation characteristics for voltage applied on valve side winding of the converter transformers, it is extraordinarily significant to study the partial discharge (PD) behavior with oil-paper insulation under combined AC-DC voltage. Therefore, this paper investigated PD inception characteristics by pulse current methods with needle-plate electrode system under combined AC-DC voltage. Furthermore, 3D electric field distributions versus combined AC-DC voltage in different ratios were calculated by Finite Element Analysis (FEA). An experimental conclusion was drew that AC partial discharge inception voltage (PDIV) in pure oil would decrease linearly with the DC component increasing but the inception voltage with oil-paper insulation appeared to be independent of DC voltage and dependent of AC voltage. And 3D electric field distribution deduced from simulation provided a supplementary proof on the experimental results. Moreover, high speed photography was used to capture emitted light produced by discharge, estimate streamer velocity (1.8 km/s) and record streamer initiation and propagation process in oil gap. Previous studies have shown that the prebreakdown phenomena involving the generation and propagation of vapor channels through the oil could be divided into a three-stage process. (C) 2012 Elsevier B.V. All rights reserved.
引用
收藏
页码:540 / 546
页数:7
相关论文
共 27 条
[1]  
Ahmed NH, 1998, CONFERENCE RECORD OF THE 1998 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, P39, DOI 10.1109/ELINSL.1998.704643
[2]  
Cevallos M., 2005, 15th IEEE International Pulsed Power Conference, P1235
[3]   An Experimental Study on the Effect of DC Bias on Streamer Initiation and Propagation in a Dielectric Liquid under Impulse Voltage [J].
Do, M. T. ;
Nysveen, A. ;
Lundgaard, L. E. ;
Ingebrigtsen, S. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2009, 16 (06) :1623-1631
[4]  
Endicott H.S., 1957, Transactions of the American Institute of Electrical Engineers, V76, P393, DOI DOI 10.1109/AIEEPAS.1957.4499574
[5]  
Fang X.T., 2007, RES DETECTION PULP F
[6]   A new stochastic model for partial discharge processes [J].
Heitz, C .
1998 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, VOLS 1 AND 2, 1998, :400-406
[7]   FORMATION OF VAPOR BUBBLES IN NONPOLAR LIQUIDS INITIATED BY CURRENT PULSES [J].
KATTAN, R ;
DENAT, A ;
BONIFACI, N .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1991, 26 (04) :656-662
[8]  
Laughton M. A., 2003, ELECT ENG REFERENCE, P7
[9]   STREAMER GENERATION AND PROPAGATION IN TRANSFORMER OIL UNDER AC DIVERGENT FIELD CONDITIONS [J].
LESAINT, O ;
TOBAZEON, R .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1988, 23 (06) :941-954
[10]   Influences of Corrosive Sulfur on Copper Wires and Oil-Paper Insulation in Transformers [J].
Li, Jian ;
He, Zhiman ;
Bao, Lianwei ;
Yang, Lijun .
ENERGIES, 2011, 4 (10) :1563-1573