An experimental comparison of heat transfer characteristic between R134-a and R22 in spray cooling

被引:37
|
作者
Chen, Shuangtao [1 ]
Liu, Jionghui [1 ]
Liu, Xiufang [1 ]
Hou, Yu [1 ,2 ]
机构
[1] Xi An Jiao Tong Univ, Sch Energy & Power Engn, Xian 710049, Peoples R China
[2] Xi An Jiao Tong Univ, State Key Lab Multiphase Flow Power Engn, Xian 710049, Peoples R China
基金
中国博士后科学基金;
关键词
Refrigerants spray cooling; R134-a; R22; Heat transfer characteristics; FLUX; ENHANCEMENT;
D O I
10.1016/j.expthermflusci.2015.03.015
中图分类号
O414.1 [热力学];
学科分类号
摘要
Spray cooling is one of the promising technologies in heat removing for high power density equipment, especially for the equipment with high heat flux surface. R134-a is one of the most prospective alternative refrigerants of R22 due to the zero ODP, low GWP, non-toxicity and non-inflammability, it is necessary to do comparative study on the heat transfer characteristics of R22 and R134-a in spray cooling. In this article, two closed loop spray cooling test rigs with the same spray nozzle are established to investigate the thermal performance of R22 spray cooling and R134-a spray cooling. The main parameters such as critical heat flux (CHF), heat transfer coefficient and target surface temperature are compared in the same thermal condition. The CHF of R134-a spray is lower due to the lower latent heat. The heat transfer coefficient of R22 spray is higher than that of R134-a spray with the same spray chamber pressure. However, R134-a spray cooling could replace R22 spray cooling in the phase change heat transfer region when the heat flux is less than 80W cm(-2). (C) 2015 Elsevier Inc. All rights reserved.
引用
收藏
页码:206 / 212
页数:7
相关论文
共 50 条
  • [1] Experimental study on the characteristics of a closed loop R134-a spray cooling
    Hou, Yu
    Liu, Jionghui
    Su, Xuemei
    Qian, Yang
    Liu, Liqiang
    Liu, Xiufang
    EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2015, 61 : 194 - 200
  • [2] Influence of chamber pressure on heat transfer characteristics of a closed loop R134-a spray cooling
    Liu, Jionghui
    Xue, Rong
    Chen, Liang
    Liu, Xiufang
    Hou, Yu
    EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2016, 75 : 89 - 95
  • [3] Experimental investigation on phase change spray cooling with R22
    Li, Mengjing
    Liu, Jionghui
    Liu, Xiufang
    Hou, Yu
    7TH INTERNATIONAL SYMPOSIUM ON MULTIPHASE FLOW, HEAT MASS TRANSFER AND ENERGY CONVERSION, 2013, 1547 : 531 - 536
  • [4] R134a and various mixtures of R22/R134a as an alternative to R22 in vapour compression heat pumps
    Karagoz, S
    Yilmaz, M
    Comakli, O
    Ozyurt, O
    ENERGY CONVERSION AND MANAGEMENT, 2004, 45 (02) : 181 - 196
  • [5] Investigation on heat transfer characteristics of R134a spray cooling
    Li, Qiang
    Tie, Peng
    Xuan, Yimin
    EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2015, 60 : 182 - 187
  • [6] Experimental study on heat transfer performance of phase change spray cooling with R134a
    Qian, Yang
    Liu, Jionghui
    Li, Mei
    Liu, Xiufang
    Hou, Yu
    Hsi-An Chiao Tung Ta Hsueh/Journal of Xi'an Jiaotong University, 2015, 49 (01): : 97 - 101
  • [7] Experimental investigation on condensation heat transfer of R22 and R410a in microtubes
    Zhang, Huiyong
    Li, Junming
    Wang, Buxuan
    Jixie Gongcheng Xuebao/Chinese Journal of Mechanical Engineering, 2008, 44 (03): : 70 - 74
  • [8] Experimental study on the heat transfer performance and dimensionless correlations for R134a spray cooling system
    Zhou, Nianyong
    Guo, Yixing
    Liu, Wenbo
    Peng, Haoping
    Lei, Yun
    Deng, Song
    Feng, Hao
    Xu, Yu
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART A-JOURNAL OF POWER AND ENERGY, 2023, 237 (03) : 550 - 558
  • [10] Comparative study on evaporator heat transfer characteristics of revolving heat pipes filled with R134a, R22 and R410A
    Yau, Y. H.
    Foo, Y. C.
    INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2011, 38 (02) : 202 - 211