Thermal performance improvement of the three aligned natural draft dry cooling towers by wind breaking walls and flue gas injection under different crosswind conditions

被引:27
作者
Jahangiri, A. [1 ]
Borzooee, A. [1 ]
Armoudli, E. [1 ]
机构
[1] Shahid Beheshti Univ, Fac Mech & Energy Engn, AC, Tehran, Iran
关键词
Three aligned heller cooling tower; Thermal performance; Combined cycle power plant; Flue gas injection; Wind breaking wall; CFD; VERTICAL DELTA RADIATORS; EFFICIENCY; SYSTEM;
D O I
10.1016/j.ijthermalsci.2018.11.028
中图分类号
O414.1 [热力学];
学科分类号
摘要
The substantial objective of using circulating cooling water in a typical power plant is to remove the heat effectively from the vapor cycle and to expel it to the environment. One of the most popular cooling systems for this purpose is the natural draft dry cooling tower (NDDCT) which is widely used in regions with the shortage of water, such as Iran. Environmental conditions affect the Heller cooling tower's performance strictly. Temperature, density, and the mass flow rate of sucked air into the cooling towers will all influence their operation. To improve the cooling tower's performance and air suction capability, it is proposed to inject the steam generators' flue gas into the tower. In this study, a single natural draft dry cooling tower incorporating the flue gas duct is modeled to study the effect of flue gas injection on the sucked air flow rate and the radiator heat transfer. Considering the buoyancy effect term, for a 3-D incompressible flow, the Navier Stokes' equations, as well as the energy equation, are solved by computational fluid dynamic method (CFD) to obtain the airflow pattern inside and outside the tower as well as the heat transfer from the radiators. The tower is assumed to be equipped with windbreak walls in one case and without it in another case so that the effect of crosswind could be investigated. Having compared the thermal performance of the towers, the results show that the thermal deficiency is more pronounced for the towers in crosswind without any flue gas injection. It is also shown that the injection of the hot flue gas (with temperature of 130 degrees C) will increase air intake and the thermal performance of the towers which, in turn, results in the reduction of the outlet water temperature. The modeling is then extended to three aligned NDDCTs to determine the effect of flue gas injection in the presence of windbreak walls under crosswind condition. Consequently, a notable promotion had been observed in all three towers thermal performance but with different ratios.
引用
收藏
页码:288 / 298
页数:11
相关论文
共 25 条
[1]   The performance of natural draft dry cooling towers under crosswind: CFD study [J].
Al-Waked, R ;
Behnia, M .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2004, 28 (02) :147-161
[2]   Comparison between evaporative cooling and a heat pipe assisted thermal loop for a commercial wind tower in hot and dry climatic conditions [J].
Calautit, John Kaiser ;
Chaudhry, Hassam Nasarullah ;
Hughes, Ben Richard ;
Ghani, Saud Abdul .
APPLIED ENERGY, 2013, 101 :740-755
[3]   Flue gas diffusion for integrated dry-cooling tower and stack system in power plants [J].
Chen, Lei ;
Yang, Lijun ;
Du, Xiaoze ;
Yang, Yongping .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2017, 114 :257-270
[4]   Experimental research of the cross walls effect on the thermal performance of wet cooling towers under crosswind conditions [J].
Chen, Youliang ;
Sun, Fengzhong ;
Wang, Hongguo ;
Mu, Nasi ;
Gao, Ming .
APPLIED THERMAL ENGINEERING, 2011, 31 (17-18) :4007-4013
[5]   The effect of the heat exchanger arrangement and wind-break walls on the performance of natural draft dry-cooling towers subjected to cross-winds [J].
duPreez, AF ;
Kroger, DG .
JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 1995, 58 (03) :293-303
[6]   EFFECT OF WIND ON PERFORMANCE OF A DRY-COOLING TOWER [J].
DUPREEZ, AF ;
KROGER, DG .
HEAT RECOVERY SYSTEMS & CHP, 1993, 13 (02) :139-146
[7]   An investigation of the effects of flue gas injection on natural draft cooling tower performance [J].
Eldredge, TV ;
Benton, DJ ;
Hodgson, JW .
JOURNAL OF ENGINEERING FOR GAS TURBINES AND POWER-TRANSACTIONS OF THE ASME, 1997, 119 (02) :478-484
[8]  
Ghaffari S., 2008, 16TH ANNUAL INTERNAT
[9]   Alternative geometry for cylindrical natural draft cooling tower with higher cooling efficiency under crosswind condition [J].
Goodarzi, M. ;
Ramezanpour, R. .
ENERGY CONVERSION AND MANAGEMENT, 2014, 77 :243-249
[10]   Heat rejection enhancement in natural draft cooling tower using radiator-type windbreakers [J].
Goodarzi, M. ;
Keimanesh, R. .
ENERGY CONVERSION AND MANAGEMENT, 2013, 71 :120-125