Two-Stage Coordinated Control Strategy of AC/DC Hybrid Power System Based on Steady-State Security Region

被引:7
作者
Zhu, Zhengguang [1 ,2 ]
Yan, Jun [1 ]
Lu, Chen [1 ]
Chen, Zhong [1 ]
Tian, Jiang [3 ]
机构
[1] Southeast Univ, Sch Elect Engn, Nanjing 210096, Peoples R China
[2] State Grid Jiangsu Elect Power Engn Consulting Co, Nanjing 210024, Peoples R China
[3] State Grid Suzhou Power Supply Co, Suzhou 215004, Peoples R China
来源
IEEE ACCESS | 2020年 / 8卷
关键词
Security; Hybrid power systems; Steady-state; Sensitivity; Optimization; Surface fitting; Power grids; AC; DC hybrid power system; steady-state security region; two-stage coordinated control strategy; security distance sensitivity; linear regression; optimization dispatch;
D O I
10.1109/ACCESS.2020.3012634
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The large-scale shift of power flow after DC blocking will seriously affect the secure operation of the system. Furthermore, after DC blocking, the system uses different control objectives in different operation stages. Therefore, a two-stage coordinated control of AC/DC hybrid power system based on steady-state security region (SSR) is proposed. Firstly, after DC blocking, the system needs to quickly restore secure operation with minimum cost. Therefore, the security correction guidance vector and the security distance sensitivity of the different control variables to it are obtained based on the linear fitting of the boundary surfaces of the SSR. The control cost of different control variables is characterized by the expansion and contraction of the SSR. According to the sensitivity of each control variable to the guidance vector and their actual adjustment ability, they are sorted and substituted into the security correction model to minimize the total adjustment cost during the process. Secondly, system will frequently be in a critical security state and not able to meet the needs of long-term secure and economic operation after security correction. Therefore, the security and economics of the system after security correction are comprehensively evaluated with the system generation cost, voltage deviation, and security margin under normal operating conditions and N-1 contingency conditions of heavy load lines. By calculating the security distance sensitivity of each control variable to the transmission limit of the crucial section, the sensitive generators and DCs that have significant effects on the transmission power of the crucial section are determined. Then the projections of security sub-region of high-sensibility control variables to optimization dispatch target, generation cost, voltage deviation, and the crucial section are depicted under different security margin, providing richer and more accurate operation information and strategic guidance for optimization dispatch. The calculation and analysis of the transformed IEEE 39-node system and the simplified actual power grid verify the correctness and effectiveness of the proposed coordinated control strategy.
引用
收藏
页码:139221 / 139243
页数:23
相关论文
共 31 条
  • [1] CHEN C, 2018, ELECT POWER AUTOM EQ, V38, P89, DOI DOI 10.1007/S11090-017-9854-2
  • [2] N-1 security assessment approach based on the steady-state security distance
    Chen, Sijie
    Chen, Qixin
    Xia, Qing
    Zhong, Haiwang
    Kang, Chongqing
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2015, 9 (15) : 2419 - 2426
  • [3] Steady-state security assessment method based on distance to security region boundaries
    Chen, Sijie J.
    Chen, Qixin X.
    Xia, Qing
    Kang, Chongqing Q.
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2013, 7 (03) : 288 - 297
  • [4] [陈中 Chen Zhong], 2019, [电力系统自动化, Automation of Electric Power Systems], V43, P73
  • [5] Model, Characterization, and Analysis of Steady-State Security Region in AC/DC Power System with a Large Amount of Renewable Energy
    Chen, Zhong
    Chen, Hui
    Zhuang, Minhui
    Bu, Siqi
    [J]. ENERGIES, 2017, 10 (08)
  • [6] A Robust Two-Level Coordinated Static Voltage Security Region for Centrally Integrated Wind Farms
    Ding, Tao
    Bo, Rui
    Sun, Hongbin
    Li, Fangxing
    Guo, Qinglai
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2016, 7 (01) : 460 - 470
  • [7] Nonlinear Coordinated Control of Multiple HVDC Links
    Eriksson, Robert
    Knazkins, Valerijs
    [J]. 2008 IEEE 2ND INTERNATIONAL POWER AND ENERGY CONFERENCE: PECON, VOLS 1-3, 2008, : 497 - +
  • [8] [顾雪平 Gu Xueping], 2017, [电力系统自动化, Automation of Electric Power Systems], V41, P17
  • [9] Fast Calculation of Power Oscillation Peak Value on AC Tie-Line After HVDC Commutation Failure
    He, Jian
    Tang, Yong
    Zhang, Jian
    Guo, Qiang
    Yi, Jun
    Bu, Guangquan
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2015, 30 (04) : 2194 - 2195
  • [10] A Flexible Power Control Strategy for Hybrid AC/DC Zones of Shipboard Power System With Distributed Energy Storages
    He, Li
    Li, Yong
    Shuai, Zhikang
    Guerrero, Josep M.
    Cao, Yijia
    Wen, Ming
    Wang, Weiyu
    Shi, Jingrong
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, 2018, 14 (12) : 5496 - 5508