Numerical studies on effects of cavity width on smoke spread in double-skin facade

被引:11
作者
Li Junmei [1 ,2 ]
Xing Xuefei [1 ,2 ]
Hu Cheng [3 ]
Li Yanfeng [1 ,2 ]
Yin Chenchen [1 ,2 ]
Liu Shanshan [1 ,2 ]
机构
[1] Beijing Univ Technol, Key Lab Urban Secur & Disaster Engn, Minist Educ, Beijing 100124, Peoples R China
[2] Beijing Univ Technol, Coll Architecture & Civil Engn, Beijing 100124, Peoples R China
[3] Beijing Municipal Inst Labour Protect, Safety & Emergency Management Lab, Beijing 100054, Peoples R China
来源
2012 INTERNATIONAL SYMPOSIUM ON SAFETY SCIENCE AND TECHNOLOGY | 2012年 / 45卷
关键词
double-skin facade; smoke movement; cavity depth; numerical study; TEMPERATURE;
D O I
10.1016/j.proeng.2012.08.225
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Double-skin facade is more and more popular in modern buildings in recently years due to it can provide the building with improved thermal and sound insulation compared with a traditional glazed facade. But fire safety is a problem, the inner glass wall broken during a fire would lead to the smoke and flame spread to the adjacent levels, this might be dangerous for the occupants in those areas. Many such projects failed to comply with the fire safety codes at present. Engineering approach similar to performance-based fire codes practicing in some countries was applied to demonstrate the design is safe. Fire hazard assessment should be supported by the further investigations on the smoke and fire spread in DSF. Cavity depth effects, one of the key factors which can influence the smoke flow in DSF would be studied by numerical method in this paper. By examining the results for cavity depth of 0.5, 1.0 and 1.5 m, it is found that a wider cavity might give better fire safety under the scenarios studied. The outer glass panel would be broken rapidly for the cavity of 0.5m deep. a Cavity depth of 1.0 m might be the most risky design comparing with the other two cavity depths studied, the inner glass panel might be broken before the outer panel, this might lead to the fire spread to the adjacent upper levels, high strength glasses should be used or other protection measures should be taken for the DSF design under this condition. Further studied should be required for an in-depth understanding the smoke and fire spread in DSF in the further. (C) 2012 The Authors. Published by Elsevier Ltd.
引用
收藏
页码:695 / 699
页数:5
相关论文
共 11 条
[1]   Theory for natural ventilation by thermal buoyancy in one zone with uniform temperature [J].
Andersen, KT .
BUILDING AND ENVIRONMENT, 2003, 38 (11) :1281-1289
[2]  
[Anonymous], 2005, NFPA 92B GUID SMOK M
[3]  
Blomsterberg Ake, 2007, EIE04135S0738652
[4]   Global energy savings in offices buildings by the use of daylighting [J].
Bodart, M ;
De Herde, A .
ENERGY AND BUILDINGS, 2002, 34 (05) :421-429
[5]  
Chow W.K., 2009, CONSTR BUILD MATER, V21, P556
[6]   Effect of cavity depth on smoke spreading of double-skin facade [J].
Chow, WK ;
Hung, WY .
BUILDING AND ENVIRONMENT, 2006, 41 (07) :970-979
[7]  
McGrattan K., 2006, NIST SPECIAL PUBLICA
[8]  
Oesterle Eberhard., 2001, Double-skin facades: integrated planning
[9]   Performance of a single glazing assembly exposed to enclosure corner fires of increasing severity [J].
Shields, TJ ;
Silcock, GWH ;
Flood, MF .
FIRE AND MATERIALS, 2001, 25 (04) :123-152
[10]  
Shields TJ., 1997, Journal of Applied Fire Science, V7, P267