Start-up behaviour of a combined air-conditioning system in cooling and heating operating modes

被引:5
作者
Jeong, Jongsoo [1 ]
Lubis, Arnas [1 ]
Saito, Kiyoshi [1 ]
Karng, Sarngwoo [2 ]
Kim, Seoyoung [2 ]
Kim, Kwangho [2 ]
机构
[1] Waseda Univ, Fac Sci & Engn, Shinjuku Ku, Tokyo 1698555, Japan
[2] Korea Inst Sci & Technol, Ctr Urban Energy Syst, Seoul, South Korea
关键词
Combined system; Start-up characteristics; Waste heat; Control; Air-conditioning; EFFECT ABSORPTION CHILLER; PUMP SYSTEM; DYNAMIC SIMULATION; ENERGY-CONSUMPTION; GAS; PERFORMANCE; BUILDINGS; CYCLE; TRANSIENTS; LIBR/H2O;
D O I
10.1016/j.enbuild.2017.11.024
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The energy demand of the commercial building sector is largely for cooling and heating and will eventually result in energy and environmental crises; therefore, enhancing the performance of the cooling and heating systems used in buildings is paramount. In response to this need, focus was set on the gas engine driven heat pump-combined system (GHPC)-consisting of a gas engine, single-stage vapour compression system, and single-effect absorption system that saves more energy as compared to a conventional gas engine-driven heat pump. However, so far, only the performance and transient characteristics of a fabricated GHPC have been investigated. Therefore, to ascertain the characteristics of the GHPC start-up dynamics under unsteady state operations so as to achieve efficient and stable start-up operation, experiments and simulations were attempted in this study. The transient behaviour from the start-up of this combined system in cooling and heating operating modes was also scrutinized. Accordingly, it was found that simulation results agreed well with experimental data. It was concluded that there were no large delayed responses in the absorption system during start-up operation when start-up of the absorption system is considered based on the system cooling capacity response after the solution pump starts. (C) 2017 Elsevier B.V. All rights reserved.
引用
收藏
页码:1346 / 1357
页数:12
相关论文
共 33 条
[1]   CO2, the greenhouse effect and global warming: from the pioneering work of Arrhenius and Callendar to today's Earth System Models [J].
Anderson, Thomas R. ;
Hawkins, Ed ;
Jones, Philip D. .
ENDEAVOUR, 2016, 40 (03) :178-187
[2]   Analysis of start-up tests of household refrigeration systems. A potential for on-line predictions of test results [J].
Andrade, Diogo E. V. ;
Negrao, Cezar O. R. .
APPLIED THERMAL ENGINEERING, 2013, 54 (01) :255-263
[3]   Small buildings, big impacts: The role of small commercial building energy efficiency case studies in 2030 Districts [J].
Barnes, Elizabeth ;
Parrish, Kristen .
SUSTAINABLE CITIES AND SOCIETY, 2016, 27 :210-221
[4]   DYNAMIC BEHAVIOR OF AN ABSORPTION HEAT-PUMP [J].
BUTZ, D ;
STEPHAN, K .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1989, 12 (04) :204-212
[5]   Limiting global warming to 2°C: What do the latest mitigation studies tell us about costs, technologies and other impacts? [J].
Dessens, Olivier ;
Anandarajah, Gabrial ;
Gambhir, Ajay .
ENERGY STRATEGY REVIEWS, 2016, 13-14 :67-76
[6]   Unsteady thermodynamic analysis for a solar driven dual storage absorption refrigeration cycle in Saudi Arabia [J].
El-Shaarawi, M. A. I. ;
Said, S. A. M. ;
Siddiqui, F. R. .
SOLAR ENERGY, 2014, 110 :286-302
[7]  
Grillakis Manolis G., 2016, Climate Services, V1, P30, DOI 10.1016/j.cliser.2016.01.002
[8]   A first-principles simulation model for the start-up and cycling transients of household refrigerators [J].
Hermes, Christian J. L. ;
Melo, Claudio .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (08) :1341-1357
[9]   Transient operation characteristics and control method in combined air-conditioning systems [J].
Jeong, Jongsoo ;
Saito, Kiyoshi ;
Karng, Sarngwoo ;
Kim, Seoyoung ;
Kim, Kwangho .
SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2017, 23 (04) :567-581
[10]   Static characteristics and efficient control of compression- and absorption-type hybrid air conditioning system [J].
Jeong, Jongsoo ;
Saito, Kiyoshi ;
Kawai, Sunao .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (03) :674-685