Observation of Natural Lightning-Induced Voltage on Overhead Power Lines

被引:22
作者
Cai, Li [1 ]
Wang, Jianguo [1 ]
Zhou, Mi [1 ]
Chen, Shaodong [1 ]
Xue, Jian [1 ]
机构
[1] Wuhan Univ, Sch Elect Engn, Wuhan 430072, Peoples R China
基金
中国国家自然科学基金;
关键词
Induced voltage; lightning current; natural lightning; overhead power line; Rusck model; INDUCED OVERVOLTAGES; MULTIPLE ARRESTERS; RETURN STROKE; DIVISION; GROUNDS; STRIKES; MODELS; FIELD;
D O I
10.1109/TPWRD.2012.2204441
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents the analysis and observation results of the induced voltage waveforms caused by nearby natural lightning on overhead power lines in the Guangzhou field experiment site during the summer of 2008. Peak values of the induced voltage for 36 natural lightning return strokes ranged from 0.21 to 3.87 kV. And the double-peak oscillation phenomenon can be found in the waveforms. The interval time of adjacent return strokes ranged from 17.1 to 430.1 ms. The average 10%-10% peak value duration time of induced voltage waveform of the first return strokes is 244.6 mu s, and that of the subsequent return strokes is 83.2 mu s. The induced voltage waveforms on the live and neutral conductors are almost the same, while the induced voltage amplitude on the live conductor is slightly larger than that on the neutral conductor. The lightning location system data indicate that the induced voltage on the live and neutral conductor may be of either positive or negative polarity, depending on the lightning ground strike points. However, the amplitude of the induced voltage calculated by the Rusck model is smaller than those of the observation results, with the former being 60% of the latter.
引用
收藏
页码:2350 / 2359
页数:10
相关论文
共 30 条
[1]   TRANSIENT-RESPONSE OF MULTI-CONDUCTOR TRANSMISSION-LINES EXCITED BY A NONUNIFORM ELECTROMAGNETIC-FIELD [J].
AGRAWAL, AK ;
PRICE, HJ ;
GURBAXANI, SH .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 1980, 22 (02) :119-129
[2]  
[Anonymous], 1993, 1024 INT EL COMM TEC
[3]  
[Anonymous], 14102004 IEEE
[4]   Induced voltage measurements on an experimental distribution line during nearby rocket triggered lightning flashes [J].
Barker, PP ;
Short, TA ;
EybertBerard, AR ;
Berlandis, JP .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (02) :980-995
[5]   Lightning-induced voltages on complex distribution systems: models, advanced software tools and experimental validation [J].
Borghetti, A ;
Gutierrez, JA ;
Nucci, CA ;
Paolone, M ;
Petrache, E ;
Rachidi, F .
JOURNAL OF ELECTROSTATICS, 2004, 60 (2-4) :163-174
[6]  
Chen Lu-wen, 2009, High Voltage Engineering, V35, P1896
[7]   CALCULATING LIGHTNING-INDUCED OVERVOLTAGES IN POWER-LINES - A COMPARISON OF 2 COUPLING MODELS [J].
COORAY, V .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 1994, 36 (03) :179-182
[8]   DISCUSSION ABOUT THE INDUCING EFFECTS OF LIGHTNING IN AN EXPERIMENTAL POWER DISTRIBUTION LINE IN MEXICO [J].
DELAROSA, F ;
VALDIVIA, R ;
PEREZ, H ;
LOZA, J .
IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (03) :1080-1089
[9]  
Eriksson A. J., 1980, SAIEE T, V71, P158
[10]   LIGHTNING - INDUCED OVERVOLTAGES ON OVERHEAD DISTRIBUTION LINES [J].
ERIKSSON, AJ ;
STRINGFELLOW, MF ;
MEAL, DV .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (04) :960-968