Fault Location in Resonant Grounded Network by Adaptive Control of Neutral-to-Earth Complex Impedance

被引:55
作者
Peng Wang [1 ]
Chen, Baichao [2 ]
Hong Zhou [1 ]
Tian Cuihua [2 ]
Bin Sun [3 ]
机构
[1] Wuhan Univ, Sch Power & Mech Engn, Wuhan 430073, Hubei, Peoples R China
[2] Wuhan Univ, Sch Elect Engn, Wuhan 430073, Hubei, Peoples R China
[3] Huanggang Power Supply Co, Econ & Technol Res Inst, Huanggang 438000, Peoples R China
关键词
Arc suppression; faulty feeder detection; fault location; neutral-to-earth complex impedance; electromagnetic hybrid petersen coil (EHPC); PETERSEN-COIL CONTROL; DISTRIBUTION-SYSTEM; FEEDER DETECTION;
D O I
10.1109/TPWRD.2017.2716955
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a fault location method based on the adaptive control of neutral-to-earth complex impedance in a resonant grounded system, whose neutral point grounds are via an electromagnetic hybrid Petersen coil (EHPC). The EHPC can be equivalent to a parallel circuit of a negative resistance and an inductance, both of which can be adjusted. When a permanent single line-to-earth fault occurs, the ground-fault current will be compensated to almost zero, and the capacitance to earth and leakage resistance of system can be measured accurately for subsequent fault location. Then, the complex impedance of EHPC is adjusted, and the faulty feeder and its faulted section can be identified online based on the characteristics that the measurements of zero-sequence admittances of points along the faulty feeder change with the system's neutral-to-ground complex impedance. The detection criterion is certain and unique, without comparing all of the feeders. This paper also proposes an adaptive jitter adjustment and decoupling control of neutral-ground complex impedance by EHPC, which is adaptive to the grounding transient resistance and is repeatable, and can ensure that the magnitude of the zero sequence parameter is large enough to be measured while without arc re-ignition, including in high impedance fault states. Simulations and experiments verified the feasibility of this fault location method and its control strategy.
引用
收藏
页码:689 / 698
页数:10
相关论文
共 20 条
[1]  
[Anonymous], 2014, C371142014 IEEE
[2]  
[Anonymous], 2007, 142 IEEE
[3]  
[Anonymous], 2007, 1057 DLT
[4]   Averaging technique for the modeling of STATCOM and active filters [J].
Bina, M. Tavakoli ;
Bhat, Ashoka K. S. .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2008, 23 (02) :723-734
[5]  
Caixu, 2003, Proceedings of the Sixth International Conference on Electrical Machines and Systems (IEEE Cat. No.03EX782), P903
[6]   Modeling and Harmonic Optimization of a Two-Stage Saturable Magnetically Controlled Reactor for an Arc Suppression Coil [J].
Chen, Xuxuan ;
Chen, Baichao ;
Tian, Cuihua ;
Yuan, Jiaxin ;
Liu, Yaozhong .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2012, 59 (07) :2824-2831
[7]   Identifying single-phase-to-ground fault feeder in neutral noneffectively grounded distribution system using wavelet transform [J].
Dong, Xinzhou ;
Shi, Shenxing .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (04) :1829-1837
[8]   A new deal for safety and quality on MV networks [J].
Griffel, D ;
Harmand, Y ;
Leitloff, V ;
Bergeal, J .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (04) :1428-1433
[9]   A Self-Isolation Method for the HIF Zone Under the Network-Based Distribution System [J].
Ko, Yun-Seok .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (02) :884-891
[10]  
Li R.X., 2002, OPERATIVE GROUNDING, P88