Double Closed-Loop Control Strategy of LCL Three-Phase Grid-Connected Inverter

被引:0
作者
Liu, Yitao [1 ]
Jin, Dianheng [1 ]
Wang, Huaizhi [1 ]
Wang, Guibin [1 ]
Peng, Jianchun [1 ]
Yin, Shan [2 ]
机构
[1] Shenzhen Univ, Coll Mechatron & Control Engn, Shenzhen, Peoples R China
[2] China Acad Engn Phys, Microsyst & Terahertz Res Ctr, Chengdu, Sichuan, Peoples R China
来源
IECON 2017 - 43RD ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY | 2017年
关键词
LCL filter; three-phase grid-connected inverter; double closed-loop current control; damping; THD; ACTIVE RECTIFIER; VOLTAGE-SOURCE; FILTER; DESIGN;
D O I
暂无
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Grid-connected inverter is an important part of the grid-connected system. Compared with the traditional L or LC filter, LCL filter has a better high-frequency harmonic attenuation performance. However, LCL filter has resonant peak, which has a great influence on the stability of the system. This paper first analyzes the effect of passive damping method on the resonance peak; then a double closed-loop control strategy with the inner loop of capacitor current and the outer loop of grid current is introduced; finally, the LCL three-phase grid-connected inverter with double-loop current control significantly reduces the Total Harmonic Distortion (THD), which verifies the feasibility of parameters design scheme of control strategy.
引用
收藏
页码:1107 / 1112
页数:6
相关论文
共 15 条
  • [1] Current control of voltage source converters connected to the grid through an LCL-filter
    Bueno, EJ
    Espinosa, F
    Rodríguez, FJ
    Ureña, J
    Cobreces, S
    [J]. PESC 04: 2004 IEEE 35TH ANNUAL POWER ELECTRONICS SPECIALISTS CONFERENCE, VOLS 1-6, CONFERENCE PROCEEDINGS, 2004, : 68 - 73
  • [2] Dong Mi, 2006, Automation of Electric Power Systems, V30, P97
  • [3] Guzman R, 2016, IEEE T POWER ELECTR, P1
  • [4] Kato T., 2015, Proc. IEEE COMPEL, Vancouver, P1
  • [5] Design and control of an LCL-filter-based three-phase active rectifier
    Liserre, M
    Blaabjerg, F
    Hansen, S
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2005, 41 (05) : 1281 - 1291
  • [6] Stability improvements of an LCL-filter based three-phase active rectifier
    Liserre, M
    Dell'Aquila, A
    Blaabjerg, F
    [J]. PESC'02: 2002 IEEE 33RD ANNUAL POWER ELECTRONICS SPECIALISTS CONFERENCE, VOLS 1-4, CONFERENCE PROCEEDINGS, 2002, : 1195 - 1201
  • [7] Design and control of three-phase PV grid connected converter with LCL filter
    Liu, Fei
    Duan, Shanxu
    Xu, Pengwei
    Chen, Guoqiang
    Liu, Fangrui
    [J]. IECON 2007: 33RD ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY, VOLS 1-3, CONFERENCE PROCEEDINGS, 2007, : 1656 - 1661
  • [8] Analysis of multiloop control strategies for LC/CL/LCL-filtered voltage-source and current-source inverters
    Loh, PC
    Holmes, DG
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2005, 41 (02) : 644 - 654
  • [9] Magueed FA, 2005, IEEE IND APPLIC SOC, P572
  • [10] Exploring Inherent Damping Characteristic of LCL-Filters for Three-Phase Grid-Connected Voltage Source Inverters
    Tang, Yi
    Loh, Poh Chiang
    Wang, Peng
    Choo, Fook Hoong
    Gao, Feng
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2012, 27 (03) : 1433 - 1443