Validation of a simple method for predicting the disinfection performance in a flow-through contactor

被引:10
作者
Pfeiffer, Valentin [1 ]
Barbeau, Benoit [1 ]
机构
[1] Polytech Montreal, Civil Geol & Min Engn Dept, Ind NSERC Chair Drinking Water, Montreal, PQ H3C 3A7, Canada
关键词
Disinfection calculation method; Escherichia coli inactivation; Chlorine contactor; T10; method; N-CSTR model; Segregated Flow Analysis; SCALE OZONE CONTACTOR; INACTIVATION; KINETICS; SYSTEMS; DESIGN; MODEL;
D O I
10.1016/j.watres.2013.11.003
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Despite its shortcomings, the T10 method introduced by the United States Environmental Protection Agency (USEPA) in 1989 is currently the method most frequently used in North America to calculate disinfection performance. Other methods (e.g., the Integrated Disinfection Design Framework, IDDF) have been advanced as replacements, and more recently, the USEPA suggested the Extended T10 and Extended CSTR (Continuous Stirred-Tank Reactor) methods to improve the inactivation calculations within ozone contactors. To develop a method that fully considers the hydraulic behavior of the contactor, two models (Plug Flow with Dispersion and N-CSTR) were successfully fitted with five tracer tests results derived from four Water Treatment Plants and a pilot-scale contactor. A new method based on the N-CSTR model was defined as the Partially Segregated (Pseg) method. The predictions from all the methods mentioned were compared under conditions of poor and good hydraulic performance, low and high disinfectant decay, and different levels of inactivation. These methods were also compared with experimental results from a chlorine pilot-scale contactor used for Escherichia coli inactivation. The T10 and Extended T10 methods led to large over- and under-estimations. The Segregated Flow Analysis (used in the IDDF) also considerably overestimated the inactivation under high disinfectant decay. Only the Extended CSTR and Pseg methods produced realistic and conservative predictions in all cases. Finally, a simple implementation procedure of the Pseg method was suggested for calculation of disinfection performance. (C) 2013 Elsevier Ltd. All rights reserved.
引用
收藏
页码:144 / 156
页数:13
相关论文
共 35 条
[21]   EVALUATION OF OZONE DISINFECTION SYSTEMS - CHARACTERISTIC TIME-T [J].
LEV, O ;
REGLI, S .
JOURNAL OF ENVIRONMENTAL ENGINEERING-ASCE, 1992, 118 (02) :268-285
[22]  
Levenspiel O., 1979, CHEM REACTION ENG, V3rd
[23]   An enhanced tanks-in-series model for interpretation of tracer tests [J].
Martin-Dominguez, A ;
Tzatchkov, VG ;
Martin-Dominguez, IR ;
Lawler, DF .
JOURNAL OF WATER SUPPLY RESEARCH AND TECHNOLOGY-AQUA, 2005, 54 (07) :435-448
[24]  
Nauman E.B., 1983, MIXING CONTINUOUS FL
[25]   Cryptosporidium log-inactivation with ozone using effluent CT10, geometric mean CT10, extended integrated CT10 and extended CSTR calculations [J].
Rakness, KL ;
Najm, I ;
Elovitz, M ;
Rexing, D ;
Via, S .
OZONE-SCIENCE & ENGINEERING, 2005, 27 (05) :335-350
[26]  
ROY D, 1981, J ENV ENG DIV-ASCE, V107, P887
[27]   Inactivation of Escherichia coli by ozone under bench-scale plug flow and full-scale hydraulic conditions [J].
Smeets, P. W. M. H. ;
van der Helm, A. W. C. ;
Dullemont, Y. J. ;
Rietveld, L. C. ;
van Dijk, J. C. ;
Medema, G. J. .
WATER RESEARCH, 2006, 40 (17) :3239-3248
[28]   Modeling Cryptosporidium parvum oocyst inactivation and bromate formation in a full-scale ozone contactor [J].
Tang, G ;
Adu-Sarkodie, K ;
Kim, D ;
Kim, JH ;
Teefy, S ;
Shukairy, HM ;
Mariñas, BJ .
ENVIRONMENTAL SCIENCE & TECHNOLOGY, 2005, 39 (23) :9343-9350
[29]  
Teefy S., 1996, Tracer studies in water treatment facilities: a protocol and case studies, P178
[30]  
USEPA, 1991, GUID MAN COMPL FILTR, P580