The 2D method for determining the temperatures field of the gas flow at the outlet of a multi-channel heat exchanger

被引:0
作者
Slesareva, E. Yu [1 ]
Elistratov, S. L. [2 ]
Ovchinnikov, V. V. [1 ]
机构
[1] SB RAS, Kutateladze Inst Thermophys, Novosibirsk 630090, Russia
[2] Novosibirsk State Tech Univ, Novosibirsk 630092, Russia
来源
ALL RUSSIAN CONFERENCE WITH THE SCHOOL FOR YOUNG SCIENTISTS THERMOPHYSICS AND PHYSICAL HYDRODYNAMICS - 2016 | 2016年 / 754卷 / 1-10期
基金
俄罗斯基础研究基金会;
关键词
D O I
10.1088/1742-6596/754/7/072004
中图分类号
O414.1 [热力学];
学科分类号
摘要
The method for experimental determination of energy efficiency in the multi-channel heat exchanger was tested. The visualization of a temperatures field has been performed to determine the thermal structure of gas flows with the use of fast-response fine-meshed wire. Thermograms of the temperature fields of the multi-channels assembly at the outlet were registered by thermal imaging camera. Results show that the 2D method provides a sufficient time resolution for the temperature field for the steady-state gas flow regime, heat generation, and nonsteady regime. The 2D method allows us to determine the gas stream parameters at the channel outlet in real time, which are necessary for determining the efficiency of the heat exchanger. Qualitative and quantitative characters of temperature changes in the thermograms are consistent with modern physical understanding of the gas flow in channels.
引用
收藏
页数:4
相关论文
共 2 条
[1]   Experimental investigation of nonisothermal gas flows in short channels [J].
Elistratov, S. L. ;
Slesareva, E. Yu. ;
Ovchinnikov, V. V. .
JOURNAL OF ENGINEERING THERMOPHYSICS, 2015, 24 (04) :346-347
[2]  
Kakac S., 2013, Convective Heat Transfer, VThird, P622