Under-Frequency Load Shedding scheme for islanded distribution network connected with mini hydro

被引:48
作者
Karimi, M. [1 ,2 ]
Mohamad, H. [3 ]
Mokhlis, H. [1 ,2 ]
Bakar, A. H. A. [2 ]
机构
[1] Univ Malaya, Fac Engn, Dept Elect Engn, Kuala Lumpur 50603, Malaysia
[2] Univ Malaya, Wisma R&D UM, UMPEDAC, Kuala Lumpur 59990, Malaysia
[3] Univ Technol MARA UiTM, Fac Elect Engn, Shah Alam 40450, Selangor, Malaysia
关键词
Distributed generation; Under-Frequency Load Shedding; Load prioritization; Rate of change of frequency; Islanding;
D O I
10.1016/j.ijepes.2012.03.017
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Under-Frequency Load Shedding (UFLS) is a common technique to maintain power system stability by removing the overload in some part of the system. The existing UFLS schemes operate successfully in the interconnected grid system. A particular approach of UFLS scheme is required for an islanded system which is known to be not as strong as the grid. This paper presents a new approach of UFLS scheme for the implementation in an islanded distribution system. The scheme is based on a combination of adaptive and intelligent techniques. The disturbance magnitude for response based and event based is treated differently: (1) event based is based on the power imbalance and (2) response based is based on the swing equation which relies on the frequency and rate of change of frequency measurement. Dynamic simulation on an intentional islanding operation is performed on an existing Malaysian network interconnected with a mini hydro generation. The objective is to investigate the effectiveness of the proposed scheme. The simulation results demonstrate that the proposed scheme is capable of improving the frequency response of the islanded system. A significant finding is that the scheme can successfully reduce the effect of power deficiency following the grid connected to islanding operation transition. (c) 2012 Elsevier Ltd. All rights reserved.
引用
收藏
页码:127 / 138
页数:12
相关论文
共 33 条
[1]   AN ADAPTIVE METHOD FOR SETTING UNDERFREQUENCY LOAD SHEDDING RELAYS [J].
ANDERSON, PM ;
MIRHEYDAR, M ;
COULTES, ME ;
TAYLOR, CW ;
RAMEY, DG .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1992, 7 (02) :647-655
[2]   Intelligent load shedding to counteract power system instability [J].
Andersson, D ;
Elmersson, P ;
Juntti, Å ;
Gajic, Z ;
Karlsson, D ;
Fabiano, L .
2004 IEEE/PES TRANSMISSION & DISTRIBUTION CONFERENCE & EXPOSITION: LATIN AMERICA, 2004, :570-574
[3]  
[Anonymous], 1994, POWER SYSTEM STABILI
[4]  
[Anonymous], INT J ELECT POWER EN
[5]  
[Anonymous], 2000, 9292000 IEEE, pi, DOI DOI 10.1109/IEEESTD.2000.91304
[6]  
[Anonymous], 2003, IEEE Std. 1547-2003, P1, DOI 10.1109/IEEESTD.2003.94285
[7]  
[Anonymous], LARG ENG SYST C POW
[8]  
[Anonymous], IEEE T POWER DELIV
[9]  
[Anonymous], IEEE T POWER SYST
[10]  
[Anonymous], INT J ELECT POWER EN