Spray characterization measurements of a pendent fire sprinkler

被引:44
作者
Zhou, Xiangyang [1 ]
D'Aniello, Stephen P. [1 ]
Yu, Hong-Zeng [1 ]
机构
[1] FM Global, Norwood, MA 02062 USA
关键词
Spray measurement; Fire sprinkler; Shadow-imaging system;
D O I
10.1016/j.firesaf.2012.07.007
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The spray patterns of a pendent fire sprinkler were characterized through experimental measurements in the near and far field of the sprinkler. A laser-based shadow-imaging system was used to measure the droplet size, velocity and number density in the spray. An array of pressure-transducer-equipped water collection tubes and containers provided a separate set of water volume flux measurements. A large-scale traverse was constructed to move the laser optics and water collection tubes and containers to the designated measurement locations. A pendent fire sprinkler with K-factor of 205 Ipm/bar(1/2) (14.2 gpm/psi(1/2)) was characterized at two discharge pressures 3.5 bar and 5.2 bar (50 and 75 psi). In the near field at 0.76 m from the sprinkler, measurements were performed in a spherical coordinate at different azimuthal and elevation angles with respect to the sprinkler deflector. In the far field, the sprays were mapped out in a 110 degrees circular sector at 3.05 m and 4.57 m below the ceiling. The shadow-imaging based water flux measurements were verified by the measurements obtained from water collection containers. The measurements show that the spatial distributions of water volume flux, droplet size and velocity of sprinkler sprays are strongly influenced by the sprinkler frame arms and the configuration of sprinkler deflector's tines and slots. For the purpose of fire protection analysis, empirical correlations were developed from the near-field measurements to prescribe the spray starting conditions for the numerical modeling of spray transport through fire plumes. The far-field measurements can be used to evaluate the spray transport calculations. (C) 2012 Elsevier Ltd. All rights reserved.
引用
收藏
页码:36 / 48
页数:13
相关论文
共 9 条
[1]  
Chan T., 1994, J FIRE PROT ENG, V6, P79, DOI DOI 10.1177/104239159400600202
[2]   DROP SIZING AND DEPTH-OF-FIELD CORRECTION IN TV IMAGING [J].
KIM, KS ;
KIM, SS .
ATOMIZATION AND SPRAYS, 1994, 4 (01) :65-78
[3]   A comprehensive methodology for characterizing sprinkler sprays [J].
Ren, Ning ;
Baum, Howard R. ;
Marshall, Andre W. .
PROCEEDINGS OF THE COMBUSTION INSTITUTE, 2011, 33 :2547-2554
[4]   The reaction of a fire plume to a droplet spray [J].
Schwille, John A. ;
Lueptow, Richard M. .
FIRE SAFETY JOURNAL, 2006, 41 (05) :390-398
[5]  
Sheppard D.T., 2002, 02838 NISTGCR
[6]   Phase Doppler interferometry measurements in water sprays produced by residential fire sprinklers [J].
Widmann, JF .
FIRE SAFETY JOURNAL, 2001, 36 (06) :545-567
[7]  
Yao C, 1980, P ENG APPL FIR TECHN, P51
[8]  
Yu H.-Z., 1986, FIRE SAFETY SCI P 1, V1, P1165
[9]   Experimental investigation of spray formation as affected by sprinkler geometry [J].
Zhou, Xiangyang ;
Yu, Hong-Zeng .
FIRE SAFETY JOURNAL, 2011, 46 (03) :140-150