Char Strength of Wool Fibre Reinforced Epoxy-Based Intumescent Coatings (FRIC)

被引:10
作者
Amir, N. [1 ]
Ahmad, F. [1 ]
Megat-Yusoff, P. S. M. [1 ]
机构
[1] Univ Teknol PETRONAS, Dept Mech Engn, Tronoh 31750, Perak, Malaysia
来源
ADVANCED MATERIALS ENGINEERING AND TECHNOLOGY | 2012年 / 626卷
关键词
intumescent; fibre; char resistance; char strength; mechanical properties; FLAME-RETARDANT; PERFORMANCE;
D O I
10.4028/www.scientific.net/AMR.626.504
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Fire protective intumescent coating cannot insulate a base material effectively if its char lacks mechanical strength. This research therefore, studied the effects of fibre reinforcement to epoxy-based intumescent coating's char strength. The fibres used include glass wool fibre, Rockwool fibre and ceramic wool fibre of 10mm length. The three formulations' mechanical performances were compared to both, a famous commercial intumescent coating and a control formulation without fibre. These coatings were fire tested up to 800 degrees C in an electric furnace for an hour. Their chars' mechanical properties were evaluated for char resistance test using predetermined weight loads. In the test, masses from 100g to 3600g were loaded continuously on top of the chars where the fibre reinforced intumescent coating (FRIC) has shown better strength and resistance to deformation. As a result, they produced lower percentage of height reduction i.e. 34% - 83% different when compared to unreinforced coating. Control char also ruptured at as low as 4N load. It was deduced that fire insulative wool fibres are effective reinforcement for improved char strength of the FRIC.
引用
收藏
页码:504 / 508
页数:5
相关论文
共 20 条
[11]  
2-9
[12]   Developments in flame retardant textiles - a review [J].
Horrocks, AR ;
Kandola, BK ;
Davies, PJ ;
Zhang, S ;
Padbury, SA .
POLYMER DEGRADATION AND STABILITY, 2005, 88 (01) :3-12
[13]   Characterization of the performance of an intumescent fire protective coating [J].
Jimenez, M. ;
Duquesne, S. ;
Bourbigot, S. .
SURFACE & COATINGS TECHNOLOGY, 2006, 201 (3-4) :979-987
[14]   Multiscale experimental approach for developing high-performance intumescent coatings [J].
Jimenez, M. ;
Duquesne, S. ;
Bourbigot, S. .
INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2006, 45 (13) :4500-4508
[15]  
Kaiser Helmut, FIRE PROTECTION IND
[16]   Fire resistance of passive fire protection coatings after long-term weathering [J].
Roberts, T. A. ;
Shirvill, L. C. ;
Waterton, K. ;
Buckland, I. .
PROCESS SAFETY AND ENVIRONMENTAL PROTECTION, 2010, 88 (01) :1-19
[17]  
*UL, 1994, 1709 UL
[18]   A review of current flame retardant systems for epoxy resins [J].
Weil, ED ;
Levchik, S .
JOURNAL OF FIRE SCIENCES, 2004, 22 (01) :25-40
[19]  
Wikipedia, 2010, MIN WOOL
[20]   Effect of Epoxy Binder on Fire Protection and Bonding Strength of Intumescent Fire Protective Coatings for Steel [J].
Yew, M. C. ;
Sulong, N. H. Ramli .
ADVANCES IN BUILDING MATERIALS, PTS 1-3, 2011, 168-170 :1228-1232