Numerical modelling of transfer phenomena in natural draft cooling towers

被引:0
作者
Rotar, M [1 ]
Drobnic, B [1 ]
Novak, M [1 ]
Sirok, B [1 ]
Donevski, B [1 ]
机构
[1] Fac Mech Engn, Ljubljana 1000, Slovenia
来源
ADVANCES IN HEAT TRANSFER ENGINEERING, PROCEEDINGS | 2003年
关键词
D O I
暂无
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
Most analyses of cooling tower operation performed so far are based on calculation of characteristic number NTU [1, 2]. The towers themselves are considered as "black-boxes" and their operation is only the evaluated as "good" or "bad". To locate particular regions of cooling tower where the operation is unsatisfactory, additional measurements are needed. These include temperatures and velocities of the airflow over the entire Surface above drift eliminators. Measurements show non-uniformity of heat transfer rate and airflow resistance over the cooling tower area. To determine influence of these non-uniformities ties to the airflow over the entire cooling tower height numerical simulations of airflow through a cooling tower were performed. Commercial software Was used for the simulations. Additional models based on measurement results were included to describe heat transfer and airflow resistance through fill system. Numerical simulation gives temperature and velocity distribution within the entire cooling tower.
引用
收藏
页码:713 / 722
页数:10
相关论文
共 10 条
[1]  
*AEA TECHN, 1999, CFX TASCFLOW THEORY
[2]  
Baker DR., 1961, J HEAT TRANSFER, V60, P339, DOI DOI 10.1115/1.3682276
[3]   A modified analysis of counter flow wet cooling towers [J].
ElDessouky, HTA ;
AlHaddad, A ;
AlJuwayhel, F .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1997, 119 (03) :617-626
[4]   Numerical study of the thermal-hydraulic performance of evaporative natural draft cooling towers [J].
Hawlader, MNA ;
Liu, BM .
APPLIED THERMAL ENGINEERING, 2002, 22 (01) :41-59
[5]  
OPRESNIK M, 1988, TERMODINAMIKA ZMESI
[6]  
ROTAR M, 2000, POSVETOVANJE ENERGET
[7]  
SIROK B, 2001, 5 WORLD C EXPT HEAT, P2243
[8]  
SIROK B, 1998, ANAL DELOVANJA HLADI
[9]  
TAN K, BUILDING ENV, V38, P91
[10]  
2000, ASHRAE SYSTEMS EQUIP, pCH36