A Novel Leakage Current Index for the Field Monitoring of Overhead Insulators Under Harmonic Voltage

被引:33
作者
Ghosh, Riddhi [1 ]
Chatterjee, Biswendu [1 ]
Chakravorti, Sivaji [1 ]
机构
[1] Jadavpur Univ, Dept Elect Engn, Kolkata 700032, India
关键词
Harmonic distortion; insulators; leakage currents; measurements; monitoring; power system harmonics; sensitivity; surface contamination; SILICONE-RUBBER; DIAGNOSTIC-TOOL; WAVE-FORMS; PERFORMANCE; COMPONENTS;
D O I
10.1109/TIE.2017.2733490
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Leakage current measurement is the most reliable and effective method for condition monitoring of overhead insulators deployed in the field. However, a major challenge in the leakage current based insulator monitoring is to interpret the indices extracted from the leakage current measurements under varying harmonic content in system voltage. This paper reports the possibility of employing the instantaneous value of time-integral of leakage current as a low-sensitive parameter for the monitoring of leakage current in overhead insulators in the presence of voltage harmonics. It has been shown that any change in the harmonic content of the system voltage has a significant influence on the harmonic characteristics of the leakage current, but has a comparatively less severe effect on the time-integral. The monitoring technique has been validated through laboratory recorded experimental data and incorporated in an online measurement device that has been tested in the laboratory.
引用
收藏
页码:1568 / 1576
页数:9
相关论文
共 26 条
[1]   Harmonic components of leakage current as a diagnostic tool to study the aging of insulators [J].
Ahmad, Hussein ;
Salam, M. A. ;
Ying, Lee Yi ;
Bashir, N. .
JOURNAL OF ELECTROSTATICS, 2008, 66 (3-4) :156-164
[2]   Level crossing analysis of leakage current envelope of polluted insulators [J].
Amarh, F. ;
Karady, G.G. ;
Sundararajan, R. .
IEEE Power Engineering Review, 2001, 21 (08) :46-49
[3]   Linear stochastic analysis of polluted insulator leakage current [J].
Amarh, F ;
Karady, GG ;
Sundararajan, R .
IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (04) :1063-1069
[4]   Odd Harmonics and Third to Fifth Harmonic Ratios of Leakage Currents as Diagnostic Tools to Study the Ageing of Glass Insulators [J].
Bashir, N. ;
Ahmad, H. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (03) :819-832
[5]   Investigations on Leakage Current and Phase Angle Characteristics of Porcelain and Polymeric Insulator under Contaminated Conditions [J].
Chandrasekar, S. ;
Kalaivanan, C. ;
Cavallini, Andrea ;
Montanari, Gian Carlo .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2009, 16 (02) :574-583
[6]   A Reinforcement-Learning-Based Fuzzy Compensator for a Microcontroller-Based Frequency Synthesizer/Vector Voltmeter [J].
Chatterjee, Amitava ;
Sarkar, Gautam ;
Rakshit, Anjan .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2011, 60 (09) :3120-3127
[7]   A new broadband microcurrent transducer for insulator leakage current monitoring system [J].
Chen, Weigen ;
Yao, Chenguo ;
Chen, Pan ;
Sun, Caixin ;
Du, Lin ;
Liao, Ruijin .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (01) :355-360
[8]  
CIGRE Task Force 33.04.03, 1994, INS POLL MON
[9]   Frequency Distribution of Leakage Current on Silicone Rubber Insulator in Salt-Fog Environments [J].
Du, B. X. ;
Liu, Yong .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (03) :1458-1464
[10]   Fundamental and low frequency harmonic components of leakage current as a diagnostic tool to study aging of RTV and HTV silicone rubber in salt-fog [J].
El-Hag, AH ;
Jayaram, SH ;
Cherney, EA .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2003, 10 (01) :128-136